9661-610
Description
I. Product Overview (Core Parameters)
1) Basic Specifications
Model: 9661-610 (115VAC, Commoned, 16 Points)
Signal Type: 115VAC Digital Output (High Voltage DO)
Channel Count: 16 Points / Board; 32 Points DO Module requires 2 Terminal Boards
Load Voltage: 115VAC ±10%, 50/60Hz
Protection: Each channel 3A Slow-Melting Fuse, with Independent FUSE Fuse Break Indicator Light
Isolation: ≥1500VAC Field - System Isolation, Anti-Surge, Anti-Interference
Common Terminal: Common Terminal (Commoned) Design, 16 Points Shared Power Circuit
Safety Level: SIL3 (IEC 61508)
Temperature: -40℃ ~ +70℃ (Industrial Wide Temperature)
Certifications: CE, UL, CSA, ATEX/IECEx
Installation: 35mm DIN Rail / Panel Mounting
Compatible Modules: 3624, 3625, 3664 (Tricon 32 Points 115VAC DO Module)
Connection Cable: Special Flat Cable (e.g. 966x-610 Series Matching Cable)
2) Panel Indicator Lights
CH01–CH16 (Green): Lit when corresponding channel output is connected
PWR (Green): Normal 115VAC Power Supply on Terminal Board
FUSE (Red): Lit when any channel fuse blows (Single Channel Position)
3) Quick Overview of 9661-610 Series (Voltage Differentiation)
9661-610: 115VAC, 16 Points, Common Terminal (High Voltage AC Main)
9661-910: 120VDC, 16 Points, Common Terminal
9662-610: 24VDC, 16 Points, Common Terminal (Low Voltage DC)
9663-610: 115VAC, 16 Points, Common Terminal (Minor Variation Version)
II. Usage Instructions (Installation / Wiring / Maintenance)
1) Installation Configuration
32 Point DO Module (3624/3625/3664): 1 Module paired with 2 9661-610 (1–16, 17–32 each 1 Module)
Installation Location: Cabinet DIN Rail, Close to 115VAC Load Side
Hot Swap: Supports Online Replacement, No Shutdown Required
2) Wiring Specifications (115VAC Load Circuit)
Live Wire L: Input from Terminal Board Common Terminal → Channel + → Load One End
Neutral Wire N: Load Other End → System Neutral
Wire Diameter: 1.5–2.5 mm² Multi-strand Copper Wire, Matched with Cold Press Terminal
Fuse: 3A Slow-Melting; FUSE Red Light On Immediately Causes Power Off and Replacement Required
3) Fault Handling
FUSE On: Corresponding Channel Short Circuit / Overload → Replace 3A Fuse
CH Off: Check Module Output, 115VAC Power Supply, Load and Wiring
PWR Off: Check Terminal Board Power Supply, Flat Cable Connection
Get a Quote