9661-610 Terminal Board (TRICONEX / Schneider Tricon SIS) Model: 9661-610 Brand: TRICONEX (Schneider Tricon Safety Instrumentation System) Location: 115VAC 16-point common digital output (DO) terminal board, specially designed for Tricon high-voltage DO modules, each with fuse + fuse blow indicator, suitable for 115VAC solenoid valves / contactors and other loads.

Description

I. Product Overview (Core Parameters)

1) Basic Specifications

Model: 9661-610 (115VAC, Commoned, 16 Points)

Signal Type: 115VAC Digital Output (High Voltage DO)

Channel Count: 16 Points / Board; 32 Points DO Module requires 2 Terminal Boards

Load Voltage: 115VAC ±10%, 50/60Hz

Protection: Each channel 3A Slow-Melting Fuse, with Independent FUSE Fuse Break Indicator Light

Isolation: ≥1500VAC Field - System Isolation, Anti-Surge, Anti-Interference

Common Terminal: Common Terminal (Commoned) Design, 16 Points Shared Power Circuit

Safety Level: SIL3 (IEC 61508)

Temperature: -40℃ ~ +70℃ (Industrial Wide Temperature)

Certifications: CE, UL, CSA, ATEX/IECEx

Installation: 35mm DIN Rail / Panel Mounting

Compatible Modules: 3624, 3625, 3664 (Tricon 32 Points 115VAC DO Module)

Connection Cable: Special Flat Cable (e.g. 966x-610 Series Matching Cable)

2) Panel Indicator Lights

CH01–CH16 (Green): Lit when corresponding channel output is connected

PWR (Green): Normal 115VAC Power Supply on Terminal Board

FUSE (Red): Lit when any channel fuse blows (Single Channel Position)

3) Quick Overview of 9661-610 Series (Voltage Differentiation)

9661-610: 115VAC, 16 Points, Common Terminal (High Voltage AC Main)

9661-910: 120VDC, 16 Points, Common Terminal

9662-610: 24VDC, 16 Points, Common Terminal (Low Voltage DC)

9663-610: 115VAC, 16 Points, Common Terminal (Minor Variation Version)

II. Usage Instructions (Installation / Wiring / Maintenance)

1) Installation Configuration

32 Point DO Module (3624/3625/3664): 1 Module paired with 2 9661-610 (1–16, 17–32 each 1 Module)

Installation Location: Cabinet DIN Rail, Close to 115VAC Load Side

Hot Swap: Supports Online Replacement, No Shutdown Required

2) Wiring Specifications (115VAC Load Circuit)

Live Wire L: Input from Terminal Board Common Terminal → Channel + → Load One End

Neutral Wire N: Load Other End → System Neutral

Wire Diameter: 1.5–2.5 mm² Multi-strand Copper Wire, Matched with Cold Press Terminal

Fuse: 3A Slow-Melting; FUSE Red Light On Immediately Causes Power Off and Replacement Required

3) Fault Handling

FUSE On: Corresponding Channel Short Circuit / Overload → Replace 3A Fuse

CH Off: Check Module Output, 115VAC Power Supply, Load and Wiring

PWR Off: Check Terminal Board Power Supply, Flat Cable Connection