8311N
Description
I. Product Overview (Core Parameters)
1) Basic Specifications
Model: 8311N (24VDC Power Module, High Density Version)
Input: 22–31VDC (Nominal 24VDC)
Output: 24VDC, Maximum 15A (Single Module)
Architecture: TMR Triple Redundancy Backplane + Dual Power Redundancy (1+1 Hot Standby)
Efficiency: ≥85%, Low Power Consumption, Excellent Heat Dissipation
Size (mm): 160 × 100 × 25 (Standard 19" Rack Slot, Full-length Card)
Weight: Approximately 1.35 kg
Temperature: -40℃ ~ +70℃ (Industrial Wide Temperature, Suitable for Harsh Environments)
Certifications: CE, UL, CSA, SIL3 (IEC 61508), ATEX
Compatibility: Tricon v9/v10/v11 Full Series (8110/8111/8121 Rack Compatible)
2) Panel Indicators (4 Lights, Intuitive Diagnosis)
PASS (Green): Normal Power Supply, Stable Output, Redundancy Synchronization
FAULT (Red): Overvoltage / Undervoltage, Overcurrent, Overheat, Internal Fault
ALARM (Yellow): Low Input Voltage, Inconsistent Redundancy, Fan Abnormal
TEMP (Red): High Temperature (≥75℃), Automatic Load Reduction Protection
3) Differences from Previous Model 8311 (N = High Density Upgrade Version)
8311 (Old Model): 12A Output, Slightly Larger Volume, v9 Early System
8311N (New Model): 15A High Current, Higher Density, Lower Power Consumption, Enhanced Temperature Resistance, v10/v11 Standard, Fully Compatible with Old Rack
II. Usage Instructions (Installation / Configuration / Maintenance)
1) Rack Slot Installation (8110/8111 Rack)
8110 Main Rack: Slot 4, Slot 5 (Must be 2 Pieces, Dual Redundancy)
8111 Expansion Rack: Slot 1, Slot 2 (Must be 2 Pieces, Dual Redundancy)
Installation: Align and push into the guide rail, lock the panel latch; Supports Hot Swap, Online Replacement without Shutdown
2) Wiring (Input 24VDC)
Input Terminal: Backplane Wiring (Rear of 8110/8111 Rack)
Wire Diameter: 1.5–2.5 mm² Multi-strand Copper Wire
Polarity: +24VDC → Positive Terminal, 0V → Negative Terminal, Do Not Reverse
Redundant Input: Recommended Two Independent 24VDC Power Supply (Improves Reliability)
3) Redundancy Configuration (Default Enabled, No Software Settings Required)
Dual Redundancy (1+1): 2 Pieces of 8311N Automatically Load Balance; Single Module Failure, Another Module 100% Carries, No Disturbance Switching
Backplane TMR Redundancy: Output Through Triple Backplane Voting, Prevents Single Point Failure
TriStation Diagnosis: Automatically Identifies Power Status, Precise Fault Location to Slot
4) Startup and Daily Check
Power On: First Connect 24VDC Input → PASS Light Lights → Rack / Module Startup
Normal State: PASS Always On,FAULT/ALARM/TEMP All Off
Common Fault Handling:
FAULT Lights On: Check Input Voltage, Wiring, Load Short Circuit; Replace Fault Module
ALARM Lights On: Low Input Voltage (<22VDC) or Inconsistent Redundancy, Check Power Supply / Module
TEMP Lights On: Poor Heat Dissipation, Clean Airflow / Dust, Improve Rack Ventilation
5) Maintenance Points
Hot Swap Replacement: Directly Pull Out Fault Module, Insert New Module; System No Shutdown, No Data Loss
Regular Inspection: Wiring Terminal Looseness, Indicator Light Status, Heat Dissipation Fan
Spares: 1:1 Redundant Standby According to Rack Quantity (e.g. 2 Racks, 2 Modules)
Get a Quote