3700A
Description
Core Configuration
Channels: 32 differential, DC coupled, non-isolated analog inputs
Input range: 0–5VDC (+6% overload range)
Signal type: Voltage (can be connected to 4–20mA through external shunt resistors)
Architecture: TMR triple redundancy, 2oo3 voting, three-channel synchronous sampling
Resolution: 12 bits
Update cycle: 55ms
Diagnosis: Overload, open circuit, short circuit, common-mode overlimit, comparison voting failure
Maintenance: Hot-swappable, online replacement without stopping operation Electrical parameters
Module power supply: 5VDC (power drawn from the back panel)
Input impedance: ≥ 1MΩ
Common mode suppression: -80dB (DC–100Hz)
Common mode voltage range: ±12V (peak)
Accuracy: ±0.15% FSR (0–60°C)
Temperature drift: ≤ ±0.005% FSR/°C
Overvoltage protection: continuous 150VDC / 115VAC
Operating temperature: –40°C ~ +70°C
Certifications: SIL3, CE, UL, CSA, ATEX Zone 2, TÜV
Power consumption: approximately 10W
Size / Weight: approximately 483×254×51mm / 2.3kg
Key features (high-density 5V AI positioning)
32-channel high density: single module 32-point differential input, saves slots and reduces costs
0–5V standard signal: directly connects to pressure / level / temperature transmitters, flow meters, valve position feedback
Differential + high common mode suppression: -80dB CMRR, strong resistance to on-site interference
TMR triple redundancy: three channels independent sampling + voting, SIL3 safety level, data reliable
Full coverage diagnosis: real-time detection of open circuits, short circuits, over-range, common mode abnormalities, panel LED + system alarm
Wide temperature + hot-swappable: suitable for harsh environments, online maintenance does not affect interlocks
Typical applications
SIS safety interlock: SIL3-level process parameter monitoring (pressure, temperature, level, flow)
Oil and gas / chemical: 32-point high-density signal acquisition, F&G fire and gas system analog quantities, containers / pipelines monitoring
Power / nuclear power: reactor parameters, boiler / turbine temperature pressure, critical equipment vibration / displacement
General safety monitoring: scenarios requiring SIL3, high density, differential anti-interference analog input with high density