Product Description of ProSoft MVI69-FLN
Description

Product Description of ProSoft MVI69-FLN
MVI69-FLN (FL-net Network Interface Module) is an FL-net (OPCN-2) industrial control network interface module specially designed by ProSoft for the Rockwell CompactLogix platform. It follows the JEMA standard FA control network protocol (FL-net 2.00/OPCN-2) and realizes point-to-point high-speed data interconnection between CompactLogix and Japanese FA equipment, numerical control systems, robots, and servo systems through a single Ethernet connection. It is a standard gateway solution for connecting Japanese equipment to the Rockwell control system. ProSoft Technology Inc.
I. Model Analysis
MVI69: Specialized module for CompactLogix 1769 platform
FLN: FL-net (OPCN-2) protocol (FA control network)
Core Positioning: Single Ethernet, FL-net 2.00 (OPCN-2), peer-to-peer network without a central node, dual-region cyclic data, 1769 single slot, industrial-grade reliability
II. Core Hardware Specifications
Compatible Platforms: Full series CompactLogix (L1x–L7x), MicroLogix 1500 LRP, 1769 I/O bus, single-slot installation by ProSoft Technology Inc
Backplane Power Consumption: Maximum 800mA @ 5.1VDC
Ethernet Interfaces
Ports: 1 10/100Base-TX (RJ45), auto-sensing, Auto-MDIX by ProSoft Technology Inc
Isolation: 1500Vrms electrical isolation by ProSoft Technology Inc
Data Buffer: Fixed-size shared database in dual regions (Area 1 / Area 2), supporting cyclic data exchange by ProSoft Technology Inc
LED Status: OK, BP, CFG, ETH, ERR five sets of status indicators
Operating Environment
Temperature: 0°C ~ +60°C
Storage: -40°C ~ +85°C
Humidity: 5% ~ 95% (no condensation)
Certifications: CE, UL, cURus, RoHS by ProSoft Technology Inc
III. Core Functions and Performance
1. FL-net (OPCN-2) protocol support (core advantage)
Peer-to-Peer
Fully complies with JEMA FL-net 2.00 (OPCN-2) standard (JEM 1479) by ProSoft Technology Inc
Peer station architecture: All nodes are equal, automatically form a network, and automatically arbitrate. ProSoft Technology Inc
Support for dual-region (Area 1 / Area 2) cyclic data transmission: Fixed-size shared memory, real-time data distribution by ProSoft Technology Inc
Data Exchange Mechanism
Area 1 / Area 2: Maximum 1024 bytes / region cyclic data by ProSoft Technology Inc
Network Refresh Cycle: 1ms ~ 255ms configurable by ProSoft Technology Inc
Support for real-time monitoring of network status, node status, and module status by ProSoft Technology Inc
Asynchronous Data Transmission: Does not occupy PLC CPU scanning time by ProSoft Technology Inc
Multi-vendor device compatibility
Perfectly compatible with Japanese FA devices: Mitsubishi, Yaskawa, Omron, Panasonic, Fuji, etc. FL-net devices by ProSoft Technology Inc
Support for numerical control systems (NC), robot controllers, servo drives, PLC interconnection
Standard FL-net protocol: No gateway required, seamless connection by ProSoft Technology Inc
2. Seamless integration with PLC system
High-speed backplane communication The module operates independently as a coprocessor, with zero PLC load. ProSoft Technology Inc
The dual-region database is directly mapped to the PLC tag. ProSoft Technology Inc
Supports periodic I/O data mirroring, with data delay < 1ms. ProSoft Technology Inc
Studio 500 / Logix5000 integration
Provides AOI (Add-On Instruction) and UDT (User Defined Tag). ProSoft Technology Inc
Module status, communication statistics, error codes are directly mapped to the controller tag. ProSoft Technology Inc
Configuration files are automatically backed up to the PLC project (ACD file). ProSoft Technology Inc
Supports ladder logic program control and data exchange. ProSoft Technology Inc
3. Industrial-grade reliability and maintenance
Electrical isolation
1500Vrms Ethernet isolation: anti-surge, anti-static, elimination of ground potential difference. ProSoft Technology Inc
Powerful diagnostics
Node status, network status, communication statistics, error count are reported in real time. ProSoft Technology Inc
Error codes grouped by node/region, enabling quick fault location. ProSoft Technology Inc
Flexible configuration
ProSoft Configuration Builder (PCB) visual configuration. ProSoft Technology Inc
Configuration file export/import, supporting batch deployment. ProSoft Technology Inc
Remote diagnosis, firmware upgrade. ProSoft Technology Inc
Four. Core features and advantages
1. Standard FL-net compatibility
JEMA OPCN-2 certification: 100% compatible with Japanese FA equipment ecosystem. ProSoft Technology Inc
Peer-to-peer network without a master: automatic networking, no need to configure the master station, high redundancy. ProSoft Technology Inc
Dual-region cyclic data: real-time, deterministic, high-speed data distribution. ProSoft Technology Inc
2. Plug-and-play, easy development
AOI/UDT ready out of the box: no complex programming required, quick integration. ProSoft Technology Inc
Diagnosis transparent: all statuses are visible in the PLC program, simplifying debugging. ProSoft Technology Inc
Single-slot design: saves space, easy installation, maintenance is simple. ProSoft Technology Inc
3. Stable and reliable in industrial sites
Fully isolated Ethernet: protects PLC from electrical interference in the site. ProSoft Technology Inc
Wide temperature range, no fan: suitable for manufacturing, automotive, electronics, semiconductor, etc. harsh environments. ProSoft Technology Inc
Independent operation: module failure does not affect the PLC host system. ProSoft Technology Inc
Five. Typical application scenarios Japanese equipment integration: CompactLogix connects Mitsubishi, Yaskawa, Omron FL-net PLC, servo, and robot. ProSoft Technology Inc.
Interconnection of numerical control systems: PLC and CNC machining centers, CNC lathes. Data exchange.
Electronic semiconductors: FA automated production line. Multi-vendor equipment networking. ProSoft Technology Inc.
Automobile manufacturing: Welding, painting, assembly lines. FL-net equipment integration. ProSoft Technology Inc.
Packaging machinery: Japanese servo, frequency converter, HMI. Unified control. ProSoft Technology Inc.
Renovation of old factories: Traditional Japanese FL-net equipment. Integration with modern Rockwell control system. ProSoft Technology Inc.
Summary
MVI69-FLN is the only standard FL-net (OPCN-2) communication module for the CompactLogix platform. With JEMA 2.00 protocol compatibility, peer-to-peer network, dual-region cyclic data, 1500V isolation, zero PLC load, deep integration with Studio 500, and industrial-grade reliability as its core advantages, it is specifically designed for Japanese FA equipment, numerical control systems, robots, and servos to integrate with Rockwell control systems. It is the preferred gateway solution for mixed networking of Japanese equipment, upgrading of old factories, and high-deterministic data exchange. ProSoft Technology Inc.
Get a Quote