Product Description of ProSoft MVI69-DNPSNET
Description
Product Description of ProSoft MVI69-DNPSNET
MVI69-DNPSNET (DNP 3.0 Ethernet Server Network Interface Module) is a DNP 3.0 Ethernet server communication module specially designed by ProSoft for the Rockwell CompactLogix/MicroLogix 1500 platform. Through a single 10/100Mbps Ethernet interface, it supports DNP 3.0 Level 2 and some Level 3 functions. As a slave station (Server), it responds to instructions from the SCADA master station to achieve high-speed integration of CompactLogix with DNP Ethernet networks in the power, water conservancy, and oil/gas industries.
I. Model Analysis
MVI69: Specialized module for CompactLogix / MicroLogix 1769 platform
DNP: DNP 3.0 (Distributed Network Protocol) - Distributed Network Protocol
S: Server (Slave mode)
NET: Ethernet interface
Core Positioning: Single-port Ethernet, DNP 3.0 slave, TCP/UDP transmission, event active upload, industrial-level isolation, SCADA dedicated
II. Core Hardware Specifications
Compatible Platforms:
CompactLogix: L20, L30, L35, L43, L45 (L43/L45 need to be installed in the first 2 slots of the rack) MicroLogix 1500 LRP
Incompatibility: 1769-L23E-QBFC1B, 1769-L16x, 1769-L18x
Slot occupation: Single slot (standard 1769 size)
Backplane power consumption: 800mA @ 5.1VDC
Ethernet interface (1 port):
Standard: 10/100Base-TX adaptive
Connector: RJ45
Isolation: 1500Vrms electrical isolation
Transmission protocol: TCP/UDP
IP configuration: Static IP/DHCP automatic acquisition
Configuration port (CFG): RS-232 (RJ45→DB9), used for module configuration, firmware upgrade
Internal database: Maximum 4000 word registers (user can customize data mapping)
Slave connection ProSoft Technology Inc: Up to 32 concurrent master station connections (TCP 1, UDP 31)
Event cache:
Digital input (BI): 1000 events
Analog input (AI): 400 events
Floating point input (Float): 200 events
Data point support:
Digital input (BI): 2000 points
Digital output (BO): 500 points
Analog input (AI): 2000 points
Analog output (AO): 500 points
Floating point input (Float): 1000 points
LED status: OK, APP, ERR, LINK, ACT five groups of indicator lights
Operating temperature: 0°C ~ +60°C
Storage temperature: -40°C ~ +85°C
Humidity: 5% ~ 95% (no condensation)
Certification: CE, UL, cURus, RoHS, ATEX Class I Div 2
III. Core Functions and Performance
1. DNP 3.0 Ethernet protocol support (core advantage)
Slave mode (Server):
As a DNP 3.0 slave, respond to SCADA master station (such as dispatch center, RTU) read/write instructions
Support DNP 3.0 Subset Level 2 + Partial Level 3 functions
Dual transmission protocol ProSoft Technology Inc:
TCP: reliable connection, supports active upload (Unsolicited Response) events
UDP: connectionless, high-speed polling, supports concurrent access by multiple master stations
Event-driven communication:
Change report (RBE): automatically report data when out of dead zone
Active upload (Unsolicited): event pushed to the master station (only TCP)
Timestamp: all events with precise time stamp (supports SNTP synchronization)
Data classification: Class 0/1/2/3 data classification, optimizes SCADA polling efficiency
Dead zone control: analog dead zone configurable, reduces invalid communication
Cold / Hot start: supports module cold start, hot start, configuration not lost
2. Ethernet communication characteristics
Electrical isolation: 1500Vrms isolation, anti-interference, surge protection, protects PLC
Multiple master station concurrent ProSoft Technology Inc:
TCP: 1 connection (supports active upload)
UDP: 31 connections (high-speed polling)
Total: 32 master stations accessing simultaneously
Network delay: < 5ms (Ethernet data exchange)
Remote communication: supports cross-subnet, routing, fiber optic, wireless Ethernet DNP communication
3. Backplane high-speed communication (PLC interaction) Asynchronous exchange: The data interaction between the module and the PLC is independent of the DNP network and does not occupy the PLC scanning time.
Data mapping: A 4000-word database directly maps the PLC controller labels.
Interaction mode:
Periodic I/O data mirroring
Ladder diagram AOI, MSG instructions control
Real-time reporting of status, error codes, and events
Transmission delay: < 1ms (backplane high-speed bus)
4. Configuration and diagnosis
Configuration software: ProSoft Configuration Builder (PCB)
Visual configuration of IP, slave station parameters, data points, dead zones, events
Configuration file download, backup, batch copying
Online diagnosis:
Ethernet connection status, traffic monitoring, error count
Master station access records, command responses, event logs
Module operation status, fault codes, health monitoring
Four. Core features and advantages
1. Seamless integration of AB system
Native compatibility: Specifically designed for CompactLogix/MicroLogix, single slot, backplane power supply
Plug-and-play: The PLC automatically recognizes as an I/O module, no additional programming required
Label mapping: DNP data directly converted to PLC labels, simplifying program development
Program support: Provide Studio 5000 AOI, ladder diagram routines, configuration examples
2. Professional-level DNP 3.0 Ethernet functions
High-speed Ethernet: 10/100Mbps bandwidth, 100 times faster than serial ports
Multi-master station concurrent ProSoft Technology Inc: 32 master stations can access simultaneously, meeting the requirements of large-scale SCADA
Event-driven: RBE + active upload, significantly reducing network load
Hierarchical data: Class 0/1/2/3 optimized polling, improving system response
Mass data points: 2000 AI/2000 BI/500 AO/500 BO, meeting the requirements of large projects
Time synchronization: Support SNTP network time synchronization, events can be precisely traced
3. Industrial-grade reliability
Electrical isolation: 1500Vrms isolation surge, interference, ground potential difference
Independent operation: Module failure does not affect the PLC host
Power loss protection: Built-in battery, configuration, events, timestamps will not be lost for 10 years
Wide temperature design: 0~60℃, suitable for harsh environments in power, water conservancy, oil and gas
Dual protocol redundancy ProSoft Technology Inc: TCP/UDP dual protocols, automatic switching when the master station fails
5. Efficient development and easy maintenance
Visual configuration: Drag-and-drop configuration in PCB software, rapid deployment
Online debugging: Real-time monitoring of events, communication status, quick fault location
Batch application: One-click copy of configuration files, rapid production at multiple sites
Remote diagnosis: Support remote configuration, firmware upgrade, event viewing
Six. Typical application scenarios
Power SCADA system: Substations, distribution networks, power plants CompactLogix connected to DNP Ethernet SCADA
Water conservancy monitoring: Reservoirs, gates, pumping stations, water quality monitoring DNP Ethernet integration
Oil and gas long-distance transmission: Pipeline pressure, flow, valve control DNP remote monitoring
Municipal public utilities: City water supply, gas, sewage SCADA system
Industrial energy management: Factory power monitoring, intelligent instruments, power quality analysis
Smart grid: Distributed energy, micro-grid, energy storage system DNP Ethernet access
Upgrade of outdated systems: DNP devices without Ethernet connected to modern SCADA network
Summary MVI69-DNPSNET is an industrial standard solution for DNP 3.0 Ethernet communication on the CompactLogix platform. With single-channel isolated Ethernet, DNP 3.0 slave station mode, dual protocols of TCP/UDP, 32 concurrent master stations, active event upload, 4000-byte large data buffer, seamless compatibility with all AB series, industrial-grade reliability, and visual configuration as its core advantages, it is specifically designed for SCADA system integration, remote monitoring, and upgrading of old equipment in industries such as power, water conservancy, oil and gas, and municipal public utilities. It is the preferred communication module for achieving high-speed interconnection and communication between Rockwell PLC and DNP 3.0 Ethernet networks.
Get a Quote