AS-B875-012 | Schneider Modicon 800 series 8-channel fixed ±10VDC differential dedicated AI module
Description
Model Explanation
B875 = 8-channel analog input series; 012 = Fixed ±10V differential special model
001: Fixed 4-20mA/1-5V single-ended
002: Multi-range single-ended universal
011: Full-range + single-ended / differential dual-purpose
012: Factory-fixed ±10VDC, default differential, incompatible with current signals, cannot be switched for current / other voltage ranges Technical Specifications
Channels: 8-channel fixed differential input, cannot be changed to single-ended; 250VAC isolation between channels, 300VAC withstand isolation between channels and the backplane
Fixed range: Only one input of **-10VDC to +10VDC**, no 4-20mA, 0-5V, 1-5V ranges, no range jumpers on the board
Input impedance: 1MΩ (full channel voltage input), no built-in 250Ω sampling resistor, cannot connect two-wire current transmitters
AD specification: 13-bit high-precision analog-to-digital conversion, 25℃ linear error ≤ ±0.05% FS, single channel accuracy approximately 17mV
Full-channel scanning: 710ms complete refresh cycle for 8 channels
Backplane power consumption: 5VDC power supply from the rack, rated 300mA for the entire unit, no need for external on-site power supply
Dimensions: 51 (W) × 203 (H) × 280 (D) mm, net weight 0.84kg
Indicators: RUN running green light, OVER over-range red light, UNDER under-range red light
Environmental parameters: Operation 0-60℃, storage -40-85℃, humidity ≤ 80% RH without condensation, IP20 protection
Interfaces and matching base
Original factory screw terminal base: AS-8535-000, compatible with differential displacement sensors, force sensors, millivolt-level instrument wiring. Core function
It is specifically designed to collect industrial differential ±10V displacement, pressure and weighing sensor signals. The differential wiring effectively suppresses long-line industrial interference. The over-limit indicator light alerts when the signal exceeds the ±10V range. It does not have a broken line current detection function. Applicable scenarios
Chemical, papermaking, and metallurgy old 984PLC renovation, the weighing module, displacement encoder, and force sensor are centrally collected at the workstations, and all on-site are ±10V differential instrument points.
Operation and Maintenance
The module is directly inserted into the 800 rack slot, without range jumper, and without single-ended/differential switching jumper; OVER red light > +10V, UNDER red light < -10V; It is prohibited to connect 4-20mA transmitters, and cannot be changed to current collection through hardware modification; It can be used in the same rack with the full series of B875, B873, and B872 modules.
Get a Quote