AS-B875-001 | Schneider Modicon 800 Series 8-channel Fixed-Type Analog Input AI Module
Description
Model Explanation
B875 = 8-channel analog input module series; 001 = Fixed dual-range specification, with one of the two options for hardware jumpers (4-20mA/1-5V); Compared with B875-002 (full-range multiple voltages/current), 001 does not have the expansion ranges of ±10V, 0-10V, etc. Technical Specifications
Channels: 8 independent electrical isolation channels, 250VAC withstand voltage between channels, 300VAC isolation between channels and the backplane
Fixed range: 4~20mA, 1~5VDC, single channel board-mounted jumper switch for mode selection
Input impedance: 1MΩ for voltage range, 250Ω precision sampling resistor built-in for current range
Resolution: 12-bit AD conversion, full-scale error ≤ ±0.05% FS
Full-channel scanning cycle: 8 channels complete acquisition takes approximately 710ms
Backplane power supply: 5VDC power taken from the rack bus, total power consumption of the machine is approximately 350mA, no external on-site power required
Dimensions: 51 (W) × 203 (H) × 280 (D) mm, net weight 0.82kg
Indicators: RUN green light for operation, OVER red light for over-range, UNDER red light for under-range
Operating conditions: 0~60℃ operation, -40~85℃ storage, humidity ≤ 80% RH without condensation, IP20 protection
Interface and matching base
Standard screw terminal base: AS-8535-000, compatible with two-wire transmitters and three-wire voltage instruments wiring. Core function
The on-site pressure, temperature and liquid level two-wire transmitters convert 4-20mA/1-5V analog signals into PLC digital quantities, completing the collection of process parameters, as well as alarm for broken lines and range over-limit. Applicable scenarios
Renovation and replacement of the old Modicon 984 system in thermal power boilers and refining and chemical plants, with all on-site points uniformly set as centralized collection positions for 4-20mA/1-5V transmitters.
Operation and Maintenance
Modules are plugged and unplugged into the I/O slots of the 800 rack. The internal jumpers of the board modify single-channel current/voltage; OVER red light = input exceeds upper limit, UNDER red light = signal is below lower limit / line break; Compatible with the entire series of B872 AO and B873 AI for mixed use in the same rack.
Get a Quote