TRICONEX 3614E Enhanced Supervised TMR Digital Output Module
Description
Model Interpretation
3614E:8-channel 24VDC non-commoned enhanced supervised relay DO; matched terminal base:3614R; full hot-swappable; compatible with 8110/8111/8112/8115/8116 standard Tricon chassis; E=Enhanced upgraded diagnostic edition。
Technical Parameters
Electrical Spec
Channel quantity:8 isolated non-common digital relay output
Rated field voltage:24VDC, operating range 22~45VDC
Per-channel continuous rated:2A DC, surge peak 10A/10ms
Off-state leakage current ≤2mA per inactive channel
Field side each channel equipped 2.5A fast-blow independent fuse
Field-backplane isolation:1500VDC galvanic isolation
Backplane consumption power<13W
Safety & Redundancy
Architecture:TMR triple-circuit 2-out-of-3 hardware voting, single path fault cannot trigger false trip or fail-safe malfunction
Certification:IEC61508 SIL3, TÜV, UL, FM, CE, ATEX safety approval
Diagnostic function:per-channel continuous load monitoring + automatic non-intrusive pulse test + feedback readback; detect open load, wire break, fuse blow, short-circuit fault; fault coverage>99.9%
SOE event timestamp ≤40ms; MTBF≥132000 operating hours
Mechanical & Environment
Single slot 3U standard Tricon module, dark blue front panel
Dimension(W×H×D):115×30×188mm, net weight≈1.2kg
Operating ambient:−40℃~+70℃; storage −55℃~+85℃; humidity 5%~95%RH non-condensing
Front panel LED: PASS, FAULT, individual channel status indicator
Core Functions
Enhanced relay isolated safety output for 24VDC ESD safety relay & critical shutdown solenoid; independent non-common channel avoids cross-channel fault interference; periodic pulse inspection verifies field loop integrity without accidental equipment action; online hot plug replacement during SIS running; real-time fault code upload to TriStation engineering software for troubleshooting。
Application Scenarios
Oil&gas onshore/offshore ESD emergency shutdown relay control; refinery HIPPS critical isolation valve drive; petrochemical reactor safety interlock loop; power plant boiler/turbine trip safety relay output; chemical plant explosion-proof solenoid emergency cut-off control。
Model Distinction
3614E:8Ch isolated relay enhanced supervised 24V DO |3624:16Ch source transistor supervised 24V DO |3625:16Ch sink transistor supervised 24V DO
Relay isolated high safety output |High-side transistor safety output |Low-side transistor safety output
Get a Quote