TRICONEX 3627 TMR Supervised Digital Output Module
Description
Model Interpretation
3627:16-channel 120VDC sink-type supervised TMR DO; matching terminal block:3627R; fully hot-swappable; compatible with 8110/8111/8112/8115/8116 rack; counterpart high-side sourcing model = 3626。
Technical Parameters
Electrical Spec
Channel count:16 commoned sink digital output
Rated field voltage:120VDC, operating range 90~132VDC, max withstand 150VDC transient
Per-channel continuous rated current:0.5A, surge current 3.5A/10ms; minimum load ≥25mA for open-circuit diagnosis
Off-state leakage ≤3.5mA per inactive channel
Isolation:2000VDC field-to-backplane galvanic isolation
Backplane power consumption<12W
Built-in auto-recovery short-circuit protection without replaceable onboard fuse
Safety & Redundancy
Architecture:3 independent circuit TMR 2oo3 hardware voting, single branch fault won’t trigger spurious trip or fail-to-shutdown
Certification:IEC61508 SIL3, TÜV, UL, FM, CE, ATEX approved
Diagnosis:channel-by-channel continuous load monitoring + automatic pulse test + output readback feedback, detect cable break, open load, short circuit, field power loss; front panel PASS/FAULT/ACTIVE/LOAD status LED, fault info uploaded to TriStation engineering software
SOE event timestamp ≤40ms; MTBF≥135000 operating hours
Mechanical & Environment
Single slot 3U standard Tricon rack module
Dimension(W×H×D):115×30×187mm, net weight≈1.15kg, dark green front panel
Operation ambient:−40℃~+70℃; storage:−55℃~+85℃
Humidity range:5%~95%RH non-condensing
Core Functions
High voltage supervised safety output for 120VDC rated field shutdown solenoid & safety relay; periodic non-intrusive pulse test verifies field loop integrity without accidental valve action; TMR fault tolerance avoids safety loop malfunction under single hardware failure; online hot plug replacement during SIS running; pinpoint channel fault location for rapid site maintenance.
Application Scenarios
Offshore & onshore oil&gas:120VDC ESD shutdown solenoid control, flare emergency cut-off valve drive
Refinery & petrochemical:HIPPS high-voltage safety relay output, reactor emergency isolation loop
Thermal power plant:turbine trip high-voltage interlock relay, boiler protection actuator control
Chemical factory:high-voltage explosion-proof solenoid emergency shutdown control
Model Comparison
3627:16Ch sink 120VDC supervised DO |3626:16Ch source 120VDC supervised DO |3623:unsupervised standard 120VDC DO
High voltage sink safety output |High voltage source safety output |General-purpose non-diagnostic auxiliary output