TRICONEX 3624 Supervised TMR Digital Output Module
Description
Model Interpretation
3624:16Ch supervised 24VDC source-type TMR digital output, turquoise green front panel
Matching terminal block:3624T(source)/3624R(sink) to define output polarity
Compatible rack: Tricon V9~V12 8110/8111/8112/8115/8116 chassis, full hot-swappable without system stop
Technical Parameters
Electrical Spec
Channel quantity:16 commoned sourcing digital output channels
Rated field voltage:24VDC, operating range 16~30VDC, max withstand 36VDC
Per channel rated current:0.7A continuous, 4.8A/10ms surge; minimum load current ≥30mA for load diagnosis
Max leakage current ≤4mA per off-channel
Isolation:1500VDC field-to-backplane galvanic isolation
Backplane power consumption<10W
Output voltage drop<1.5VDC typical
Self-recovery short-circuit protection, no onboard fuse design
Safety & Redundancy
Architecture:2oo3 triple modular redundant hardware voting, single sub-circuit fault no false output action
Certification:IEC61508 SIL3, TÜV, UL, FM, CE, ATEX certified
Diagnosis core:per-channel continuous load monitoring + periodic pulse test + output feedback readback; detect field open load, short circuit, power loss, cable break; PASS/FAULT/ACTIVE/POWER/LOAD LED indicator on front panel, fault upload to TriStation engineering software
SOE timestamp ≤40ms
MTBF≥142000 operating hours
Mechanical & Environment
Single slot 3U Tricon rack module
Dimension(W×H×D):115×30×187mm, net weight≈1.1kg
Front panel:turquoise green with multi-status LED
Operating ambient:-40℃~+70℃; storage:-55℃~+85℃
Humidity:5%~95%RH non-condensing
Core Functions
Supervised safety DO for critical ESD solenoid/shutdown valve, real-time field circuit health inspection via pulse test function
TMR fault-tolerant output avoids spurious trip or fail-to-shutdown under single hardware failure
Online hot swap replacement during SIS running, channel-level fault location for quick field troubleshooting
TriStation software configure output logic, monitor real-time channel status and historical fault log
Application Scenarios
Oil&Gas Onshore/Offshore:Wellhead ESD shutdown solenoid, flare ignition valve safety drive
Refinery & Petrochemical:Reactor emergency cut-off valve, HIPPS safety relay output control
Thermal Power Plant:Boiler fuel trip valve, turbine emergency protection digital output
Chemical Plant:Reaction vessel overpressure shutdown actuator control
Brief Difference
3624(16Ch supervised 24V SDO,load pulse test,SIL3)|3604(32Ch non-supervised standard DO,no load diagnosis)
Critical safety shutdown output|General auxiliary digital output