TRICONEX 3704E High Density TMR Analog Input Module
Description
Model Interpretation
3704E: 64-channel non-isolated single-ended AI, software configurable 0–5V/0–10V, enhanced industrial grade variant
Compatibility: Tricon V9~V12 chassis(8110/8111/8112/8115/8116), full hot-swappable
Color Mark: Copper brown front panel(different from yellow 3720/3721)
Core Difference vs 3720: No field isolation, fixed 12-bit resolution, longer 75ms full scan rate, dual voltage range option(0–5V/0–10V)
Technical Parameters
Electrical Spec
Input Mode: 64 channels commoned single-ended, non-galvanic isolation between field and backplane
Signal Range: Software selectable 0~5VDC or 0~10VDC (+6% overrange tolerance)
Resolution: Fixed 12-bit ADC
Full Module Update Rate: 75ms for all 64 channels
Basic Accuracy: <±0.25%FSR at 0~60℃ ambient
DC Input Impedance: Min 30MΩ; typical off-state resistance 30kΩ
Overvoltage Protection: Continuous withstand 150VDC/115VAC surge
Inter-channel isolation resistance: Typical 200kΩ between channels
Backplane power consumption: ≤11.5W @24VDC
Safety & Redundancy
Architecture: 2oo3 triple modular redundancy voting, single circuit fault no loop outage
Certification: IEC61508 SIL3, TÜV, UL, CE, FM certified
Diagnostics: Per-channel open/short/overrange + TMR mismatch continuous diagnosis, fault coverage>99.9%
SOE timestamp resolution ≤40ms
MTBF ≥135000 operating hours
Mechanical & Environment
Form: Standard single slot 3U Tricon rack module
Dimension(W×H×D):114×30×186mm
Net Weight:≈1.3kg
Front LED Indicator: PASS, FAULT, ACTIVE (no FIELD lamp compared with isolated 3720 series)
Operating Temp:-40℃~+70℃; Storage:-55℃~+85℃
Humidity:5%~95%RH non-condensing
Core Functions
High-density economical analog collection for bulk pressure/temp/flow transmitter voltage signals without strict isolation requirement
Two-range voltage switching via TriStation software to adapt different site transmitter specifications
TMR redundant fault-tolerant acquisition to satisfy SIL3 safety interlock requirement for ESD system
Online hot swap replacement without SIS system stop, fast fault positioning by channel-level self-diagnosis
Lower unit cost per channel for large I/O count SIS expansion project
Applications
Oil&Gas Onshore/Offshore: Bulk wellhead process monitoring, general ESD analog collection without isolation demand
Refinery & Chemical Plant: Mass reactor/tank regular PV monitoring for HIPPS safety interlock
Thermal Power Plant: Boiler auxiliary conventional analog monitoring for unit safety protection
SIS Retrofit: High channel density cost-effective upgrade replacing multiple low-density AI cards
Brief Contrast
3704E(64Ch non-isolate,0~5/10V,75ms)|3720TMR(64Ch isolate,0~5V/4-20mA,10ms)|3721(32Ch isolate differential,±5V,10ms)
Cost-effective dense general AI|Isolated high-speed high-density AI|Isolated differential bipolar precision AI