TRICONEX 3720TMR (64‑Ch High‑Density TMR Analog Input Module)
Description
Model Interpretation
3720TMR (3720): 64‑Ch TMR Analog Input, single‑ended, 0–5V/0–20mA
P/N: 3720 (TMR = triple modular redundancy)
Compatibility: Tricon v10.2–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable
Key Difference from 3721: 64 single‑ended channels (vs. 32 differential on 3721); lower cost per channel; yellow color code
Technical Parameters
Electrical & Input
Input Type: Single‑ended, isolated; voltage or current
Voltage Range: 0–5VDC (±6% over‑range, 0–5.3VDC)
Current Range: 0–20mA (±6% over‑range, 250Ω shunt required)
Channels: 64, single‑ended; field‑to‑backplane isolation (≥800VDC)
Resolution: 12‑bit (standard) or 14‑bit (high) programmable
Accuracy: <±0.15% FSR (0–60°C)
Input Impedance: 140kΩ (DC, typical)
Over‑Range Protection: 150VDC / 115VAC continuous
Update Rate: 10ms (all channels)
Backplane Power: 24VDC, ≤12W
Isolation: 1,500VDC field‑to‑backplane galvanic isolation
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics: Per‑channel continuous diagnostics (open/short, over‑range, TMR mismatch); fault coverage >99.9%; SOE ≤40ms
MTBF: >140,000 hours
Mechanical & Environmental
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~0.8 kg
Color Code: Yellow (high‑density AI identifier)
Operating Temp: −40°C to +70°C
Storage Temp: −55°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, FIELD
Fault Detection: Over/under‑range, TMR deviation, channel open/short
Core Functions
64‑Channel High‑Density Analog Acquisition
64 single‑ended inputs for 0–5V or 0–20mA; ideal for high‑I/O safety loops needing cost‑effective, dense signal capture.
Programmable Precision (12/14‑bit)
Switch between 12‑bit (faster, standard) and 14‑bit (higher precision) to balance speed and accuracy in SIL3 applications.
TMR Fault‑Tolerant Safety Monitoring
Three independent circuits with 2oo3 voting; eliminates single‑point failures for ESD/F&G/BMS loops.
Isolated & Robust Signal Conditioning
1,500VDC isolation and high CMRR suppress ground loops/EMI; built for harsh oil/gas/chemical environments.
Hot‑Swap & Online Maintenance
Replace module without shutdown; per‑channel diagnostics and SOE logging support IEC 61511 compliance.
Applications
Oil & Gas: ESD/F&G systems; high‑density pressure/flow monitoring (offshore/onshore)
Chemical/Refining: HIPPS loops; large‑scale reactor/column analog monitoring
Power Generation: Turbine/boiler ESD; BMS with dense sensor arrays
SIS Retrofits: High‑channel‑count upgrades for Tricon v10.2+ chassis
Get a Quote