TRICONEX 3708E (8‑Channel TMR Thermocouple Analog Input Module)
Description
Model Interpretation
3708E: 8‑Ch TMR Thermocouple Input, isolated differential, TMR architecture
P/N: 3708E (E = enhanced diagnostic & extended temp range)
Compatibility: Tricon v9–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable
Key Difference from 3700/3701: Thermocouple‑specific input (vs. voltage‑only on 3700/3701)
Technical Parameters
Electrical & Input
Input Type: Isolated differential, thermocouple (K/J/E/T/R/S/B)
Channels: 8, isolated (channel‑to‑channel & field‑to‑backplane)
Input Range: ±20mV (thermocouple signal range)
Resolution: 16‑bit + sign
Accuracy: ±0.1% FSR (0–60°C, includes CJC)
Input Impedance: ≥10MΩ
Common‑Mode Rejection: ≥−120dB (DC–100Hz)
Response Time: <2s (all channels updated)
Backplane Power: 24VDC, ≤10W
Isolation: 1,500VDC field‑to‑backplane galvanic isolation
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, IECEx
Diagnostics: Per‑channel continuous diagnostics (open/short circuit, out‑of‑range, TMR mismatch); fault coverage >99.9%
MTBF: >120,000 hours
Mechanical & Environmental
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~1.2 kg
Color Code: Black (thermocouple module identifier)
Operating Temp: −40°C to +70°C
Storage Temp: −55°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Protection Class: IP20 (panel‑mounted)
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM
Fault Detection: Thermocouple open/short, over/under‑range, CJC fault, TMR deviation
Core Functions
8‑Channel High‑Precision Thermocouple Measurement
Directly interfaces with 7 common thermocouple types; built‑in CJC ensures accurate temperature readings from −200°C to +1800°C (sensor‑dependent).
TMR Fault‑Tolerant Temperature Monitoring
Three independent measurement circuits with 2oo3 voting; eliminates single‑point failures for SIL3 ESD/F&G/BMS temperature loops.
Isolated & Noise‑Immune Signal Conditioning
1,500VDC isolation and −120dB CMRR suppress ground loops and EMI; ideal for high‑noise oil/gas/chemical environments.
Hot‑Swap & Online Maintenance
Replace module without shutdown; per‑channel diagnostics and SOE logging support IEC 61511 compliance.
Continuous Sensor Health Monitoring
Detects thermocouple open/short circuits and drift; prevents nuisance trips from faulty temperature sensors.
Applications
Oil & Gas: ESD/F&G systems; furnace/reactor temperature monitoring (offshore/onshore)
Chemical/Refining: High‑temperature process loops; reactor/cracker thermocouple monitoring
Power Generation: Boiler/turbine ESD; high‑temperature combustion chamber monitoring
SIS Retrofits: Drop‑in upgrade for Tricon chassis requiring direct thermocouple input
Get a Quote