TRICONEX 3701TMR (32‑Channel TMR Analog Input, 0–10VDC)
Description
Model Interpretation
3701TMR (3701): 32‑Ch TMR Analog Input, 0–10VDC, differential
P/N: 3701 (TMR is integral to the model)
Compatibility: Tricon v9–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable
Key Difference from 3700: 0–10VDC input range (vs. 0–5V on 3700)
Technical Parameters
Electrical & Input
Input Type: Differential, DC‑coupled
Voltage Range: 0–10VDC (strict, no extended tolerance)
Channels: 32, differential (non‑isolated channel‑to‑channel)
Resolution: 12 bits
Accuracy: <±0.15% FSR (0–60°C)
Input Impedance: ≥30MΩ (DC)
Response Time: <55ms (all channels updated)
Backplane Power: 24VDC, ≤15W (full load); logic power <5W
Isolation: 1,500VDC field‑to‑backplane galvanic isolation
Common‑Mode Rejection: ≥−80dB (DC–100Hz)
Input Protection: 150VDC / 115VAC continuous
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics: Per‑channel continuous diagnostics; fault coverage >99.9%; SOE ≤40ms
MTBF: >150,000 hours
Mechanical & Environmental
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~1.2 kg (2.6 lbs)
Color Code: Dark Blue (distinguishes from 3700’s dark red)
Operating Temp: −40°C to +70°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM
Fault Detection: Over/under‑range, TMR deviation, channel fault
Core Functions
32‑Channel High‑Precision 0–10VDC Input
Monitors 0–10V analog transmitters (pressure, temp, flow, level); 12‑bit resolution and ±0.15% accuracy ensure reliable safety loop measurements.
TMR Fault‑Tolerant Analog Monitoring
Three independent measurement circuits with 2oo3 voting; eliminates single‑point failures for SIL3 ESD/F&G/BMS applications.
High Noise Immunity & Isolation
1,500VDC field‑to‑backplane isolation and −80dB common‑mode rejection suppress ground loops and EMI in harsh industrial environments.
Hot‑Swap & Online Maintenance
Replace module without system shutdown; per‑channel diagnostics and SOE logging support IEC 61511 compliance.
Continuous Channel Diagnostics
Detects over/under‑range, signal drift, and TMR mismatches; up to 2 faulty channels allowed without module replacement.
Applications
Oil & Gas: ESD/F&G systems; pressure/temperature monitoring on pipelines and platforms with 0–10V transmitters
Chemical/Refining: HIPPS loops; reactor/column analog signal monitoring
Power Generation: Turbine ESD; boiler BMS with 0–10V pressure/flow transmitters
SIS Retrofits: High‑density analog monitoring in existing Tricon chassis
Get a Quote