TRICONEX 3701TMR (32‑Channel TMR Analog Input, 0–10VDC)
June 02, 2026

TRICONEX 3701TMR (32‑Channel TMR Analog Input, 0–10VDC)

Product Description The 3701TMR (3701) is a SIL3‑certified TMR analog input module for Tricon v9–v12 SIS chassis, providing 32 differential, DC‑coupled input channels for 0–10VDC analog signals. It’s the 0–10V counterpart to the 3700/3700A, designed for high‑precision monitoring of pressure, temperature, flow, and level transmitters in safety‑critical ESD/F&G/BMS loops, with 12‑bit resolution and TMR fault tolerance

Description

Model Interpretation

3701TMR (3701): 32‑Ch TMR Analog Input, 0–10VDC, differential

P/N: 3701 (TMR is integral to the model)

Compatibility: Tricon v9–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable

Key Difference from 3700: 0–10VDC input range (vs. 0–5V on 3700)

Technical Parameters

Electrical & Input

Input Type: Differential, DC‑coupled

Voltage Range: 0–10VDC (strict, no extended tolerance)

Channels: 32, differential (non‑isolated channel‑to‑channel)

Resolution: 12 bits

Accuracy: <±0.15% FSR (0–60°C)

Input Impedance: ≥30MΩ (DC)

Response Time: <55ms (all channels updated)

Backplane Power: 24VDC, ≤15W (full load); logic power <5W

Isolation: 1,500VDC field‑to‑backplane galvanic isolation

Common‑Mode Rejection: ≥−80dB (DC–100Hz)

Input Protection: 150VDC / 115VAC continuous

Redundancy & Safety

Architecture: Triple Modular Redundancy (TMR), 2oo3 voting

Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM

Diagnostics: Per‑channel continuous diagnostics; fault coverage >99.9%; SOE ≤40ms

MTBF: >150,000 hours

Mechanical & Environmental

Form Factor: 3U, 19” rack, 1 slot

Dimensions (W×H×D): 114 × 30 × 185 mm

Weight: ~1.2 kg (2.6 lbs)

Color Code: Dark Blue (distinguishes from 3700’s dark red)

Operating Temp: −40°C to +70°C

Storage Temp: −40°C to +85°C

Humidity: 5%–95% RH, non‑condensing

Diagnostics & Indicators

LEDs: PASS, FAULT, ACTIVE, TMR, ALARM

Fault Detection: Over/under‑range, TMR deviation, channel fault

Core Functions

32‑Channel High‑Precision 0–10VDC Input

Monitors 0–10V analog transmitters (pressure, temp, flow, level); 12‑bit resolution and ±0.15% accuracy ensure reliable safety loop measurements.

TMR Fault‑Tolerant Analog Monitoring

Three independent measurement circuits with 2oo3 voting; eliminates single‑point failures for SIL3 ESD/F&G/BMS applications.

High Noise Immunity & Isolation

1,500VDC field‑to‑backplane isolation and −80dB common‑mode rejection suppress ground loops and EMI in harsh industrial environments.

Hot‑Swap & Online Maintenance

Replace module without system shutdown; per‑channel diagnostics and SOE logging support IEC 61511 compliance.

Continuous Channel Diagnostics

Detects over/under‑range, signal drift, and TMR mismatches; up to 2 faulty channels allowed without module replacement.

Applications

Oil & Gas: ESD/F&G systems; pressure/temperature monitoring on pipelines and platforms with 0–10V transmitters

Chemical/Refining: HIPPS loops; reactor/column analog signal monitoring

Power Generation: Turbine ESD; boiler BMS with 0–10V pressure/flow transmitters

SIS Retrofits: High‑density analog monitoring in existing Tricon chassis


Get a Quote