TRICONEX 3506XTMR (Supervised 24VDC DI, TMR, 32‑Channel)
Description
Model Interpretation
3506XTMR: 3506X = Supervised DI, 24VDC, 32‑point; TMR = Triple Modular Redundancy
P/N: 3506X (3506XTMR is full designation)
Compatibility: Tricon v9–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable
Key Feature: 32 supervised channels, 24VDC, per‑channel open/short/wire‑break detection, advanced glitch filtering
Technical Parameters
Electrical & Input
Input Type: Dry/wet contact, 24VDC nominal
Voltage Range: 18–32VDC (max 36VDC transient)
Channels: 32, individually supervised (no group isolation)
Input Current: ~5mA (on‑state)
Response Time: <10ms all channels; diagnostic glitch ≤2ms (500µs typical)
Backplane Power: 24VDC, ~180mA
Isolation: 1,500VDC field‑to‑backplane galvanic isolation
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics: >99.99% fault coverage; per‑channel open/short/wire‑break alarm; SOE ≤40ms
MTBF: >160,000 hours
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~2.5 kg (5.5 lbs)
Mounting: Plug‑in backplane, hot‑swappable
Color Code: Dark Red
Environmental
Operating Temp: −40°C to +70°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM, LINE‑FAULT
Fault Detection: Open circuit, short circuit, wire break, TMR deviation, stuck state
Core Functions
32‑Channel Supervised 24VDC Input
Monitors ESD pushbuttons, limit switches, proximity sensors; per‑channel line supervision detects broken wires, loose connections, or short circuits—critical for high‑safety loops where hidden wiring faults risk system failure。
Enhanced TMR Fault Tolerance
Three independent input circuits with 2oo3 voting; higher diagnostic coverage than 3505E reduces spurious trips and improves safety integrity for SIL3 applications。
Advanced Glitch Filtering & Noise Immunity
Filters transient glitches ≤2ms to prevent false alarms; 1,500VDC isolation rejects ground loops and electrical noise—ideal for harsh oil/gas/chemical environments。
Hot‑Swap & Online Maintenance
Replace module without shutdown; real‑time diagnostics and SOE logging support regulatory compliance (IEC 61511)。
Continuous Field Circuit Health Monitoring
Beyond standard open/short detection, per‑channel wire‑break monitoring ensures full visibility of field wiring—eliminating “hidden fault” risks in safety loops。
Applications
Oil & Gas: ESD/F&G systems with critical 24V sensors; offshore platforms requiring 100% wiring supervision
Chemical/Refining: HIPPS loops; process interlocks with high‑integrity discrete signals
Power Generation: Turbine ESD; boiler BMS with safety‑critical 24V devices
SIS Upgrades: Replace 3505E for higher diagnostic coverage; SIL3 systems needing per‑channel wire‑break detection
Get a Quote