TRICONEX 3564 (64‑Point TMR Digital Input Module, 24VDC)
Description
Model Interpretation
3564: 64‑Point TMR Digital Input Module, 24VDC, commoned, high‑density
P/N: 3564 (base model, TMR is integral)
Compatibility: Tricon v9–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable
Key Feature: 64 channels (commoned, non‑isolated channel‑to‑channel), 24VDC only, 1,500VDC field‑to‑backplane isolation
Technical Parameters
Electrical & Input
Input Type: Dry/wet contact, DC‑coupled (24VDC nominal)
Voltage Range: 15–30VDC (max 36VDC)
Channels: 64, commoned (no channel‑to‑channel isolation)
Input Current: 2–3mA (on‑state)
Hysteresis: 4VDC (typical)
Response Time: <2ms (on/off)
Backplane Power: 24VDC, ~160mA
Isolation: 1,500VDC field‑to‑backplane galvanic isolation
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics: >99.9% fault coverage; open/short detection; SOE (≤40ms resolution)
MTBF: >145,000 hours
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~2.1 kg (4.6 lbs)
Mounting: Plug‑in backplane, hot‑swappable
Color Code: Dark Red
Environmental
Operating Temp: −40°C to +70°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM
Fault Detection: Open/short circuit, TMR deviation, stuck‑state
Core Functions
64‑Point High‑Density 24VDC Safety Input
Accepts 15–30VDC signals (ESD pushbuttons, limit switches, proximity sensors); 64 commoned channels minimize slot usage for large safety systems, reducing cost per point.
TMR Fault‑Tolerant Voting
Three independent input circuits per signal; 2oo3 voting eliminates single‑point failures—critical for SIL3 ESD/F&G/BMS loops.
High Noise Immunity & Isolation
1,500VDC field‑to‑backplane isolation rejects ground loops and electrical noise; ideal for harsh industrial environments.
Hot‑Swap & Online Maintenance
Replace module without system shutdown; supports online diagnostics and SOE logging for regulatory compliance.
Cost‑Effective Large‑Scale I/O
Optimized for high‑count 24V safety signal arrays; commoned design simplifies wiring and reduces system complexity.
Applications
Oil & Gas: Large‑scale ESD/F&G systems; high‑count 24V safety switches and detectors
Chemical/Refining: Complex process interlocks; dense discrete safety signal arrays
Power Generation: Turbine ESD; boiler BMS with numerous 24V safety interlocks
SIS Retrofits: Maximize I/O capacity in existing Tricon chassis; reduce slot count for large loops