TRICONEX 3505E (Enhanced Digital Input, EDI, 24VDC, Wire‑Break Detection)
Description
Model Interpretation
3505E: Enhanced Digital Input (EDI), 24VDC, 32‑point, TMR, wire‑break detection
P/N: 3505E (base)
Compatibility: Tricon v9–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable
Key Feature: 32 channels (8 groups × 4 commoned), 24VDC, wire‑break (open‑circuit) detection
Technical Parameters
Electrical & Input
Input Type: Dry/wet contact, 24VDC only (no AC)
Voltage Range: 20–42.5VDC (max 42.5VDC)
Channels: 32, commoned in 8 groups (4 channels/group), group‑isolated
Input Current: ~6mA (on‑state)
Backplane Power: 24VDC (20.4–28.8VDC), ~150mA
Isolation: 1,500VDC group‑to‑backplane galvanic isolation
Special Feature: Wire‑break detection (open‑circuit monitoring for each channel)
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics: >99.9% fault coverage; SOE (≤40ms resolution); open/short detection + wire‑break alarm
MTBF: >150,000 hours
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~2.4 kg (5.3 lbs)
Mounting: Plug‑in backplane, hot‑swappable
Color Code: Dark Red
Environmental
Operating Temp: −40°C to +70°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM, WIRE‑BREAK
Fault Detection: Open/short circuit, TMR deviation, wire‑break (open‑circuit) per channel
Core Functions
24VDC Safety Input with Wire‑Break Detection
Designed for 24VDC field devices (ESD pushbuttons, limit switches, proximity sensors); unique wire‑break detection identifies broken wires or disconnected sensors—critical for high‑safety loops where open circuits pose risks.
TMR Fault‑Tolerant Voting
Three independent input circuits per signal; 2oo3 voting eliminates single‑point failures—compliant with SIL3 ESD/F&G/BMS requirements.
Group Isolation & Noise Immunity
8 isolated groups reduce cross‑talk; opto‑isolation rejects ground loops and electrical noise—suitable for oil/gas/chemical plants.
Hot‑Swap & Online Maintenance
Replace module without system shutdown; supports online diagnostics and SOE logging for regulatory compliance.
Enhanced Diagnostics for Safety Compliance
Beyond standard open/short detection, per‑channel wire‑break monitoring ensures 100% visibility of field circuit health—ideal for IEC 61511 compliance.
Applications
Oil & Gas: ESD systems with 24V safety switches; F&G detectors requiring wire‑break monitoring
Chemical/Refining: Process interlocks with critical 24V discrete signals; HIPPS loops
Power Generation: Turbine ESD; boiler BMS with safety‑critical 24V sensors
SIS Retrofits: Upgrade 3503E systems to add wire‑break detection for higher safety integrity