TRICONEX 3502E (TMR Digital Input Module, 48V AC/DC, Self‑Test)
Description
Model Interpretation
3502E: TMR Digital Input Module, 48V AC/DC, with Self‑Test, SIL3
P/N: 3502E (base; “TMR” is its core architecture, not a separate suffix)
Compatibility: Tricon v9–v12 chassis (8110/8111/8112/8115/8116); hot‑swappable
Key Upgrade: 32 channels (8 groups × 4 commoned), 35–95V AC/DC, self‑test for de‑energize‑to‑trip circuits
Technical Parameters
Electrical & Input
Input Type: Dry/wet contact, 48V AC/DC nominal (35–95V AC/DC)
Channels: 32, commoned in 8 groups (4 channels per group)
Input Current: 6–9mA (on‑state)
Backplane Power: 24VDC (20.4–28.8VDC), ~150mA
Isolation: 1,500VDC channel‑to‑backplane galvanic isolation
Frequency: DC or 47–63Hz AC
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics: >99.9% fault coverage; self‑test for off‑state detection; SOE (≤40ms resolution)
MTBF: >150,000 hours
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~0.9 kg (2.0 lbs)
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: −40°C to +70°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM
Fault Detection: Open/short circuit, channel mismatch, TMR deviation, self‑test fault
Core Functions
48V AC/DC Safety Input for SIS
Accepts 35–95V AC/DC field signals (ESD pushbuttons, F&G detectors, interlock switches); 32 commoned channels (8 groups) reduce wiring complexity。
TMR Fault‑Tolerant Voting
Three independent input circuits per signal; 2oo3 voting eliminates single‑point failures—critical for SIL3 ESD/F&G/BMS loops。
Self‑Test for De‑Energize‑to‑Trip
Unique self‑test verifies detection of off‑state transitions, ensuring safety for “de‑energize‑to‑trip” systems (standard in most SIS)。
Hot‑Swap & Online Maintenance
Replace module without system shutdown; supports online diagnostics and SOE logging for compliance。
High‑Noise Immunity
Opto‑isolation + TMR design rejects ground loops and electrical noise—ideal for harsh oil/gas/chemical environments。
Applications
Oil & Gas: Offshore ESD/F&G systems; 48V AC/DC safety switches
Chemical/Refining: Process interlocks; medium‑voltage discrete safety signals
Power Generation: Turbine ESD; boiler safety interlocks
SIS Retrofits: Upgrade legacy Tricon v9–v12 systems with SIL3 48V DI
Get a Quote