TRICONEX 3501E (TMR Digital Input Module, 115V AC/DC)
Description
Model Interpretation
3501E: TMR Digital Input Module, 115V AC/DC, SIL3
P/N: 3501E (base)
Compatibility: Tricon v9–v11 chassis (8110/8111/8112/8115); hot‑swappable
Key Feature: 32 isolated non‑commoned points, 115V AC/DC nominal, TMR voting
Technical Parameters
Electrical & Input
Input Type: Dry/wet contact (115V AC/DC nominal)
Voltage Range: 90–155V AC/DC; DC or 47–63Hz AC
Channels: 32 isolated, non‑commoned (opto‑isolated per channel)
Input Current: ~8mA per channel (on‑state)
Backplane Power: 24VDC (20.4–28.8VDC), ~150mA
Isolation: 2500VDC channel‑to‑backplane galvanic isolation
Redundancy & Safety
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Safety Certification: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics: >99.9% fault coverage; SOE (≤40ms resolution)
MTBF: >150,000 hours
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~1.84 kg (4.06 lbs)
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: −40°C to +70°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Protection: IP65/IP67 (dust/water resistant)
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM
Fault Detection: Open/short circuit, channel mismatch, TMR deviation
Core Functions
High‑Voltage Digital Input for SIS
Accepts 115V AC/DC field signals (ESD pushbuttons, F&G detectors, interlock switches); 32 isolated channels eliminate common‑mode faults。
TMR Fault‑Tolerant Voting
Three independent input circuits per signal; 2oo3 voting ensures no single‑point failure impacts safety loop—critical for SIL3 ESD/F&G。
Hot‑Swap & Online Maintenance
Replace module without system shutdown; supports online diagnostics and SOE logging for compliance。
High‑Noise Immunity
Opto‑isolation + TMR design rejects ground loops and electrical noise—ideal for harsh oil/gas/chemical environments。
Applications
Oil & Gas: Offshore ESD/F&G systems; 115V AC/DC safety switches
Chemical/Refining: Process interlocks; high‑voltage discrete safety signals
Power Generation: Turbine ESD; boiler safety interlocks
SIS Retrofits: Upgrade legacy Tricon v9–v11 systems with SIL3 115V DI