TRICONEX 3009 (UMP – Enhanced Main Processor)
Description
Model Interpretation
3009: UMP (Enhanced Main Processor), Trident series, SIL3
P/N: 3009 (base)
Compatibility: Trident chassis (8115/8116); firmware v12+; hot‑swappable
Key Upgrade: 80 MHz MPC860, 64 MB DRAM, 16 MB Flash, dual 25 Mbps TriBus
Technical Parameters
Electrical & Power
Power: 24VDC backplane (20.4–28.8VDC), ~6W typical
Isolation: 500VDC port‑to‑backplane galvanic isolation
Redundancy: TMR 2oo3 hardware voting; 3 modules mandatory
Processing & Memory
Processor: Triple 32‑bit MPC860 RISC, 80 MHz
DRAM: 64 MB (ECC‑protected)
Flash: 16 MB (application/firmware)
SRAM: 128 KB (battery‑backed, data retention)
Scan Time: 2–10 ms (fastest in 300x series)
TriClock: ±1 s/day (battery‑backed)
Communication Interfaces
TriBus: Dual 25 Mbps (redundant inter‑processor/I/O bus)
Diagnostic: Isolated RS‑232 (25‑pin, local TriStation)
Ethernet: Optional (via comm module)
I/O Capacity: Up to 512 I/O points per system
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~0.9 kg (2.0 lbs)
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: 0°C to +60°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM
Diagnostics: >99.9% coverage; ECC error correction; real‑time fault logging
Core Functions
Ultrafast TMR Safety Logic
Triple 80 MHz cores execute complex logic; 2oo3 voting eliminates single‑point failures—ideal for large/complex SIL3 ESD/F&G/BMS.
Massive Memory for Large Programs
64 MB DRAM + 16 MB Flash supports huge safety logic and data logging; 2–10 ms scan enables instant safety responses.
Dual Redundant TriBus
Two 25 Mbps buses ensure fault‑tolerant processor/I/O synchronization for large systems.
Hot‑Swap & Online Maintenance
Replace modules without shutdown; supports online programming/firmware updates via TriStation 1131.
Comprehensive Diagnostics & SOE
Real‑time fault logging, ECC tracking, and SOE for compliance; alarms to DCS/HMI.
Applications
Oil & Gas: Mega‑project ESD/F&G; large offshore platforms
Chemical/Refining: Complex reactor safety; high‑integrity BMS/ESD
Power Generation: Critical turbine BMS; boiler protection
SIS New Builds: Trident system standard processor for large‑scale SIL3
Get a Quote