TRICONEX 3007 Main Processor Module
June 02, 2026

TRICONEX 3007 Main Processor Module

Product Description The 3007 is legacy TMR CPU module for Tricon v9 series SIS, serving as core logic solver installed inside 8110 main chassis. It executes user safety application program, controls I/O bus communication and 2-out-of-3 hardware voting for SIL3 safety interlock systems including ESD, FGS and BMS. It is predecessor model of 3006 processor.

Description

Model Interpretation

3007: Original EMP main processor; PN:3000307‑100; compatible with Tricon v9.0~v9.4; drop-in replacement by 3006 for upgrade projects.

Technical Parameters

Electrical

Backplane powered 24VDC; typical power consumption ~9W; galvanic isolation between diagnostic port and internal circuit.

Memory & Performance

Triple redundant CPU core; ECC protected RAM 1MB; flash memory 1MB; typical logic scan range 20~100ms related to program size.

Interface

TriBus internal high-speed bus for inter-CPU synchronization and I/O data exchange; one isolated RS232 diagnostic port for local TriStation download and troubleshooting; no external Ethernet or serial communication port.

Mechanical

Single slot plug-in module; hot swappable; weight approx 0.75kg.

Environment

Operating temperature 0~+60°C; storage −40~+85°C; humidity 5%~95% non-condensing; certified SIL3 IEC61508, TÜV, UL, FM.

Indicator

Front LEDs: PASS, FAULT, RUN, TMR status; continuous built-in self-test and fault diagnosis.

Core Functions

Complete triple modular redundancy 2oo3 voting to avoid single point failure; schedule periodic I/O data refresh and safety logic computation; store SOE and fault diagnostic information; support online download via TriStation engineering software.

Applications

Refinery, petrochemical, power plant legacy Tricon v9 SIS system spare replacement; old site maintenance and spare inventory.