TRICONEX 3006 (Main Processor Module, EMP II)
Description
Model Interpretation
3006: EMP II Enhanced Main Processor, TMR, SIL3
P/N: 3006 (base), 3000xxx series variants
Family: 3006 (EMP II) vs 3007 (1MB RAM, older)
Compatibility: Tricon 8110/8111/8112 chassis; hot‑swappable; TMR (3‑module set) / non‑TMR modes
Key Distinction: 3‑channel TMR with ECC memory; dedicated TriBus for inter‑processor sync; diagnostics coverage >99.9%
Technical Parameters
Electrical & Power
Power: 24VDC (backplane, 20.4–28.8VDC), ~400mA, 10W typical
Isolation: 500VDC port‑to‑backplane galvanic isolation
Redundancy: TMR 2oo3 hardware voting; 3 modules required for full TMR
Processing & Memory
Processor: Triple independent 32‑bit RISC (25MHz clock)
RAM: 2MB ECC‑protected (battery‑backed, ±2s/day drift)
Flash: 2MB protected (application firmware)
Scan Time: 10–50ms (depends on program size)
Communication Interfaces
TriBus: 4Mbps, 16‑bit DMA (inter‑processor/I/O sync)
Diagnostic Serial: Isolated RS‑232 (25‑pin, 500VDC isolation)
I/O Bus: Dual Intel 80C31 I/O processors (12MHz, 32KB EPROM each)
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 114 × 30 × 185 mm
Weight: ~0.8 kg (1.8 lbs)
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: 0°C to +60°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, TMR, ALARM
Diagnostics: >99.9% coverage; real‑time fault detection; ECC error correction
Protection: ESD, surge, short‑circuit, overtemperature
Core Functions
TMR Fault‑Tolerant Safety Logic
Three synchronized 32‑bit processors execute identical logic; 2oo3 hardware voting eliminates single‑point failures—critical for SIL3 ESD/F&G/BMS.
ECC Memory Integrity
ECC‑protected RAM/Flash corrects single‑bit errors and detects double‑bit errors, preventing data corruption in safety loops.
High‑Speed System Management
TriBus (4Mbps) ensures tight processor/I/O sync; 10–50ms scan times support fast safety responses.
Hot‑Swap & Online Maintenance
Replace modules without shutdown; TriStation 1131 enables online programming/firmware updates.
Comprehensive Diagnostics & SOE
Real‑time fault logging, ECC error tracking, and SOE for compliance; propagates alarms to DCS/HMI.
Applications
Oil & Gas: Offshore ESD/F&G; platform‑wide safety logic
Chemical/Refining: High‑integrity BMS/ESD; reactor safety control
Power Generation: Boiler BMS/Turbine TMC; critical turbine safety
SIS Upgrades: Replaces older Tricon processors (e.g., 3007) in legacy systems
Get a Quote