TRICONEX 4352A (TCM, Tricon Communication Module)
Description
Model Interpretation
4352A: TCM, 2×MT‑RJ fiber Ethernet (100 Mbps) + 4×DB‑9 serial (RS‑232/485)
P/N: 3000590‑xxx series
Family: 4352A (fiber TCM; vs 4351B copper TCM, 4329 legacy coax NCM)
Compatibility: Tricon 8110/8111/8112 chassis; hot‑swappable; TMR/non‑TMR
Key Distinction: Fiber‑only Ethernet (MT‑RJ); no RJ45; for long‑haul/EMI‑heavy areas
Technical Parameters
Electrical & Power
Power: 24VDC (backplane, 20.4–28.8VDC), 1.0A max, ~5W
Isolation: 500VDC port‑to‑backplane; galvanic isolation for all ports
Redundancy: TMR 2oo3 voting; dual‑port network redundancy support
Communication Interfaces
Ethernet (2×MT‑RJ, 100 Mbps fiber):
NET 1: Safety network (peer Tricons, time sync, TSAA)
NET 2: Open network (DCS, OPC, TriStation, SOE)
Cable: 62.5/125 μm multimode fiber; Max distance: 2 km (no repeater)
Serial (4×DB‑9, RS‑232/422/485):
Speed: Up to 115.2 kbps per port; Total throughput: 460.8 kbps
Protocols: Modbus RTU/ASCII, TriStation, custom serial
Protocols: Modbus TCP/RTU, TSAA, TriStation, SNTP, OPC UA
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 483 × 127 × 305 mm
Weight: ~2.3 kg
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: 0°C to +60°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics & Indicators
LEDs: PASS, FAULT, ACTIVE, FIRM, LINK1, LINK2, TX/RX per port
Monitoring: Link status, error counters, TMR voting health, time sync
Protection: ESD, surge, short‑circuit, overtemperature
Core Functions
Fiber Optic Long‑Distance Communication
2×100 Mbps MT‑RJ fiber ports enable 2 km safe communication in high‑EMI areas (e.g., near motors, power substations), avoiding copper cable noise issues.
SIL3 Fault‑Tolerant Networking
TMR 2oo3 voting ensures no single‑point failure; all data paths comply with SIL3 for safety‑critical loops (ESD, F&G).
Ethernet + Serial Multi‑Protocol Integration
Simultaneously supports Modbus TCP (fiber) and Modbus RTU (serial) to connect DCS, HMI, PLCs, and legacy serial devices in one module.
Hot‑Swap & Redundancy
Online replacement without shutdown; dual‑fiber ports support network redundancy for maximum uptime.
System Diagnostics & SOE
Enables SOE logging, remote diagnostics, and TriStation programming; propagates system alarms to external hosts.
Applications
Oil & Gas: Offshore ESD/F&G; long‑distance safety communication between platforms
Chemical/Refining: High‑EMI areas (furnaces, compressors); fiber connection to DCS
Power Generation: Boiler BMS/Turbine TMC; peer Tricon sync via fiber
Legacy System Upgrades: Replacing 4329 coax with modern fiber while retaining serial device support
Get a Quote