TRICONEX 4509 (Hiway Interface Module, HIM)
Description
Model Interpretation
4509: Hiway Interface Module (HIM), 2×Isolated Hiway Channels, SIL3, TMR
P/N: 3000590‑xxx series
Family: 4509 (legacy Hiway gateway; no Ethernet/serial)
Compatibility: Tricon 8110/8111/8112 chassis; hot‑swappable; works with TMR/non‑TMR configurations
Key Distinction: Proprietary Hiway only (vs 4119A/4351B with serial/Ethernet)
Technical Parameters
Electrical & Power
Power: 24VDC (backplane‑supplied, 20.4–28.8VDC), 1.5A max per Hiway leg
Isolation: AC‑coupled isolation between 2 Hiway channels; 2500Vrms port‑to‑backplane
Redundancy: TMR 2oo3 communication channels (matches Tricon controller TMR); hot‑spare capable
Communication Interfaces
Hiway Channels (2×Proprietary): Isolated, AC‑coupled; connects to Honeywell TDC‑2000 (Data Hiway) / TDC‑3000 (Hiway Gateway/LCN)
Hiway Addresses: 8 configurable addresses (matches DHP slot structure)
Data Refresh: <0.5 seconds (full data update)
No Ethernet/Serial: No TCP/IP, Modbus, or RS‑232/485 support (Hiway‑only)
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 145 × 120 × 55 mm
Weight: ~0.8 kg
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: 0°C to +60°C (non‑condensing)
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: IEC 61508 SIL3, TÜV, UL, CE, ATEX, FM
Diagnostics & Indicators
LEDs: PASS, FAULT, HWY1, HWY2
Monitoring: Hiway link status, error counters, TMR voting health, channel isolation
Protection: ESD, surge, short‑circuit, overtemperature
Core Functions
Legacy Honeywell DCS Gateway
The only Tricon module natively supporting Honeywell Hiway/Data Hiway; bridges Tricon SIS to TDC‑2000/TDC‑3000 without middleware.
SIL3 Fault‑Tolerant Communication
TMR 2oo3 voting across 2 isolated Hiway channels eliminates single‑point failures; all data paths are SIL3‑compliant for safety loops.
Real‑Time Data Exchange
8 Hiway addresses and <0.5s refresh enable fast, reliable sharing of safety data (ESD, BMS, HIPPS) with Honeywell DCS.
Hot‑Swap & Redundancy
Online replacement without shutdown; dual Hiway channels support network redundancy for maximum availability.
Backward Compatibility
Works with legacy Tricon v9–v11 chassis and 3503/3504 I/O racks; avoids costly full‑system upgrades for facilities with older Honeywell DCS.
Applications
Oil & Gas: Tricon ESD/F&G integration with Honeywell TDC‑3000 DCS; remote wellsite safety data exchange
Power Generation: Boiler BMS/Turbine TMC connectivity to Honeywell TDC‑2000; safety loop monitoring
Chemical/Refining: SIL3 safety data sharing between Tricon SIS and Honeywell DCS; batch process safety
Legacy System Modernization: Connecting pre‑Ethernet Honeywell DCS to modern Tricon SIS without DCS replacement
Get a Quote