TRICONEX 4119A (EICM, Enhanced Intelligent Communication Module)
Description
Model Interpretation
4119A: EICM, 4×Serial (RS‑232/422/485) + 1×Parallel, Isolated, SIL3
P/N: 3000589‑xxx series
Family: 4119 (base) / 4119A (isolated ports, enhanced firmware)
Compatibility: Tricon 8110/8111/8112 chassis; max 2 modules per chassis (one logical slot)
Key Distinction: No Ethernet (vs 4351B with 2×Ethernet)
Technical Parameters
Electrical & Power
Power: 24VDC (backplane, 20.4–28.8VDC)
Isolation: 500VDC per port; 2500Vrms port‑to‑backplane
Redundancy: TMR‑compatible (works with Tricon’s 2oo3 voting)
Communication Interfaces
Serial Ports (4 × DB‑9): RS‑232/RS‑422/RS‑485, 1200–19.2Kbps
Protocols: Modbus RTU/ASCII (Master/Slave), TriStation 1131
RS‑485: 1 master → up to 32 slaves; 1200m max distance
Parallel Port (1 × Centronics): Isolated, for printer output
No Ethernet: No TCP/IP, Modbus TCP, or SNTP support
Mechanical
Form Factor: 3U, 19” rack, 1 slot
Dimensions (W×H×D): 483 × 127 × 305 mm
Weight: ~0.8–1.0 kg
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: 0°C to +60°C
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: SIL3 (IEC 61508), TÜV, UL, CE
Diagnostics & Indicators
LEDs: PASS, FAULT, COM1–COM4
Monitoring: Port status, baud rate, Modbus error counters
Protection: ESD, surge, short‑circuit, overtemperature
Core Functions
Serial‑Only SIL3 Communication
4 isolated serial ports for Modbus RTU/ASCII and TriStation; ideal for connecting to serial‑only devices (RTU meters, legacy PLCs, HMIs) without Ethernet.
Isolated Printer Connectivity
1 isolated Centronics port for hardcopy logging/reporting (critical for safety loop audit trails).
Modbus Master/Slave Flexibility
Each serial port configurable as Modbus Master/Slave; up to 7 Modbus Masters per chassis.
TMR Compatibility & Hot‑Swap
Works with Tricon’s TMR safety architecture; online replacement without shutdown.
Applications
Oil & Gas: Serial RTU/flow meters, legacy PLCs, safety valve positioners
Power Generation: Turbine serial governors, boiler serial sensors, printer logging
Chemical/Refining: Modbus RTU analyzers, local HMIs, batch printer reports
Legacy System Integration: Connecting pre‑Ethernet devices to modern Tricon SIS
Get a Quote