TRICONEX 3807(Bipolar TMR Analog Output Module)
June 02, 2026

TRICONEX 3807(Bipolar TMR Analog Output Module)

Product Description The 3807 is a 4‑channel, TMR bipolar high‑current analog output (AO) module for Tricon v9–v11 SIS chassis (8110/8111/8112). It is specialized for bidirectional, high‑force actuators (e.g., servo valves, hydraulic actuators, DC motor direction/speed control) requiring −60mA to +60mA bipolar drive. TMR 2oo3 voting delivers SIL3 fault tolerance; 13‑bit resolution and strong diagnostics ensure precision in safety‑critical motion/positioning loops.

Description

Model Interpretation

3807: 4‑Ch Bipolar Analog Output, TMR, High‑Current (−60…+60mA)

P/N: 3000590‑xxx series

Family: 3807 (only variant; no “E/H” suffix)

Compatibility: Tricon 8110/8111/8112 chassis; not a drop‑in for 3805/3806 (different signal range/pinout)

Technical Parameters

Electrical

Channels: 4 isolated bipolar analog outputs (common return, DC‑coupled)

Output Range: −60mA to +60mA (bipolar, 120mA FSR); no voltage mode

Resolution: 13‑bit

Accuracy: <0.25% FSR (0–60°C, FSR=120mA)

Max Load: 150Ω (at ±60mA)

Loop Power: 24VDC nominal (20.4–28.8VDC, reverse‑voltage protected)

Isolation: 2500Vrms channel‑to‑backplane

Redundancy: TMR 2oo3 voting (three independent legs; switch time <10ms on leg failure)

Mechanical

Dimensions (W×H×D): 483 × 25.4 × 453 mm (19” rack, 1 slot)

Weight: ~4 kg

Mounting: Plug‑in backplane, hot‑swappable

Environmental

Operating Temp: 0°C to +60°C

Storage Temp: −40°C to +85°C

Humidity: 5%–95% RH, non‑condensing

Certifications: SIL3 (IEC 61508), TÜV, UL, ATEX/IECEx

Diagnostics & Indicators

LEDs: PASS, FAULT, ACTIVE, LOAD, PWR1, PWR2 (module status)

Monitoring: Per‑channel current readback; open/short‑circuit detection; overrange/underrange alarms

Protection: Overvoltage (+36VDC continuous), overcurrent, short‑circuit, overtemperature

Fail‑Safe: Configurable hold‑last‑value or preset safe‑value on fault

Core Functions

Bipolar High‑Current Drive (−60…+60mA)

Delivers bidirectional, high‑current output for servo valves, hydraulic actuators, DC motors (direction + speed control) and other specialized field devices needing positive/negative drive.

TMR SIL3 Safety Architecture

Triple‑modular redundancy with 2oo3 voting eliminates single‑point failures; meets SIL3 for safety‑critical motion/positioning loops.

13‑Bit Precision & Per‑Channel Diagnostics

13‑bit resolution ensures accurate positioning; real‑time current readback and fault detection validate output integrity.

Hot‑Swap & Redundancy Compatibility

Online replacement without shutdown; compatible with redundant I/O architectures for maximum availability.

Applications

Oil & Gas: ESD‑critical servo valves, hydraulic actuator control, subsea valve positioning

Power Generation: Steam turbine hydraulic governors, boiler feedwater valve servos, generator excitation control

Chemical/Refining: Reactor agitator DC motor control, precision distillation column valve positioning

Industrial Motion: Bidirectional actuators, servo systems, high‑force positioning requiring ±60mA drive