TRICONEX 3806E(TMR Analog Output Module)
June 02, 2026

TRICONEX 3806E(TMR Analog Output Module)

Product Description The 3806E is an 8‑channel, high‑precision TMR analog output (AO) module for Tricon v9–v11 SIS chassis (8110/8111/8112). It’s the high‑density, cost‑optimized sibling of the 3805E/3805H, designed for general‑purpose SIL3 analog control loops (valves, actuators, I/P converters). TMR 2oo3 voting eliminates single‑point failures; enhanced diagnostics ensure loop integrity for safety‑critical applications.

Description

Model Interpretation

3806E: 8‑Ch Enhanced Analog Output, TMR, High‑Density

P/N: 3000589‑xxx series

Family: 3806 (base), 3806E (enhanced diagnostics/accuracy)

Compatibility: Tricon 8110/8111/8112 chassis; drop‑in replacement for 3805E in standard loops

Technical Parameters

Electrical

Channels: 8 isolated analog outputs (common return, DC‑coupled)

Output Ranges: 4–20mA (default, +6% overrange to 22mA); 0–20mA; 0–5V; 0–10V (per‑channel configurable)

Resolution: 12‑bit

Accuracy: <0.25% FSR (4–20mA, 0–60°C); typical ±0.1% FSR

Response Time: ≤2ms (full‑scale step)

Loop Power: 24VDC nominal (max 42.5VDC, reverse‑voltage protected)

Isolation: 2500Vrms channel‑to‑backplane

Redundancy: TMR 2oo3 voting (three independent legs)

Mechanical

Dimensions (W×H×D): 483 × 25.4 × 453 mm (19” rack, 1 slot)

Weight: ~4 kg

Mounting: Plug‑in backplane, hot‑swappable

Environmental

Operating Temp: 0°C to +60°C (derated to 55°C at full load)

Storage Temp: −40°C to +85°C

Humidity: 5%–95% RH, non‑condensing

Certifications: SIL3 (IEC 61508), TÜV, UL, ATEX/IECEx

Diagnostics & Indicators

LEDs: PASS, FAULT, ALARM (module + per channel)

Monitoring: Loop current/voltage feedback; open/short‑circuit detection; overrange/underrange alarms

Protection: Overvoltage, overcurrent, short‑circuit, overtemperature

Fail‑Safe: Configurable hold‑last‑value or preset safe‑value on fault

Core Functions

TMR SIL3 Safety: Triple‑modular redundancy with 2oo3 voting ensures no single‑point failure; meets SIL3 for safety loops.

High‑Density Analog Control: 8 channels per slot (same as 3805E) with standard accuracy, ideal for high I/O count systems.

Cost‑Effective Performance: Balances precision and cost for non‑inductive, general‑purpose loads (vs. 3805H’s high‑inductive focus).

Hot‑Swap & Redundancy: Online replacement without shutdown; compatible with redundant I/O architectures.

Loop Diagnostics: Real‑time feedback monitoring validates output integrity, reducing unplanned downtime.

Applications

Oil & Gas: ESD valve control, pipeline pressure regulation, burner management (non‑inductive valves).

Power Generation: Boiler feedwater valve modulation, BMS fuel valve control, turbine auxiliary actuators.

Chemical/Refining: Distillation column valve positioning, reactor auxiliary control loops.

Industrial Automation: High‑channel‑count SIL3 loops, general‑purpose analog output, cost‑sensitive safety systems.


Get a Quote