TRICONEX 3805H(3805HTMR)
Description
Model Interpretation
3805H: Enhanced Analog Output, High Inductive Load, TMR
3805HTMR: Commonly known in the market, emphasizing TMR triple redundancy
P/N: 3000588-xxx series
Compatibility: Tricon 8110/8111/8112 chassis, fully compatible with 3805E applications Technical Parameters
Electrical
Channel: 8-channel isolated analog output
Output range: 4–20mA (default, can be up to 22mA); 0–20mA; 0–5V; 0–10V (each channel can be set)
Resolution: 12 bit
Accuracy: <0.25% FSR (0–60℃), typical ±0.1% FSR
Drive capability: Enhanced for inductive load driving (stronger than 3805E)
Loop power supply: 24VDC (maximum 42.5VDC, reverse voltage protection)
Isolation: 2500Vrms (channel to backplane)
TMR: Three-channel independent, 2oo3 voting Mechanical
Dimensions (W×H×D): 483 × 25.4 × 453 mm (19-inch rack, 1 slot)
Weight: Approximately 3.65 kg
Installation: Backplane hot-swappable, supports online replacement Environmental
Operating temperature: 0℃ ~ +60℃
Storage temperature: −40℃ ~ +85℃
Humidity: 5%–95% RH, no condensation
Certifications: SIL3 (IEC61508), TÜV, UL, ATEX/IECEx Diagnostics
LED: PASS / FAULT / ALARM (module + per channel)
Loop monitoring: Current loop self-check, load open/closed circuit detection
Protection: Overvoltage, overcurrent, short circuit, overtemperature
Self-calibration: Channel-level drift compensation Core Functions
TMR Triple Redundancy Fault Tolerance
Three independent DA + voting, any channel failure does not affect the output, meeting SIL3 safety circuits requirements.
Enhanced Inductive Load Drive
Compared with 3805E, it has stronger drive capability and better surge suppression, suitable for solenoid valves, servos, electric valves, etc.
Full Loop Diagnosis + Loop Self-Check
Each channel has an independent current loop to verify the authenticity of the output; open circuit / short circuit of the load will trigger an alarm promptly.
Hot Swap and Redundancy Architecture Compatibility
Online replacement without downtime; can be combined with redundant I/O architecture. Applications
Oil and Gas: ESD/F&GS valve control, compressor anti-surge protection, electromagnetic valve group drive
Power: Turbine actuators, boiler feedwater valves, excitation control
Chemical: Reactor temperature/pressure valves, distillation tower control, high inductive load actuators
Safety-critical: SIL3 loop, highly reliable analog output, frequently operated valve control