TRICONEX 3805E Enhanced Analog Output Module
Description
Model Interpretation
3805E
3805E: Enhanced Analog Output Module (TMR, 8‑ch)
Common P/N: 3000316‑110
Family: 3805 (standard AO), 3805E (enhanced diagnostics/accuracy)
Compatibility: Tricon v9–v11 chassis (8110/8111/8112), TMR safety systems
Technical Parameters
Electrical
Channels: 8 isolated analog outputs (common return, DC‑coupled)
Output Ranges: 4–20mA (default, +6% overrange to 22mA); 0–20mA; 0–5V; 0–10V (per‑channel configurable)
Resolution: 12‑bit
Accuracy: <0.25% FSR (4–20mA, 0–60°C); typical ±0.1% FSR
Response Time: ≤2ms (full‑scale step)
Loop Power: Nominal +24VDC (max +42.5VDC, reverse‑voltage protected)
Isolation: 2500Vrms channel‑to‑backplane
Redundancy: TMR 2oo3 voting (three independent legs)
Mechanical
Dimensions (W×H×D): 483 × 25.4 × 453 mm (19” rack, 1 slot)
Weight: 3.65 kg
Mounting: Plug‑in backplane, hot‑swappable
Environmental
Operating Temp: 0°C to +60°C (32°F to 140°F)
Storage Temp: −40°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: SIL3 (IEC 61508), TÜV, UL, ATEX/IECEx
Diagnostics & Indicators
LEDs: PASS, FAULT, ALARM (module + per channel)
Monitoring: Continuous loop current/voltage comparison; open/short‑circuit detection; overrange/underrange alarms
Protection: Overvoltage, overcurrent, short‑circuit, overtemperature
Core Functions
TMR Safety & Accuracy: 2oo3 voting maintains control if one leg fails; 12‑bit resolution + <0.25% FSR accuracy for critical loops。
Flexible Analog Output: Configurable 4–20mA/0–10V ranges to suit valves, actuators, and I/P converters。
Hot‑Swap & Redundancy: Online replacement without shutdown; compatible with redundant I/O architectures。
Enhanced Diagnostics: Real‑time loop health monitoring with fault logging and SOE (sequence of events) reporting。
Applications
Oil & Gas: ESD/F&GS valve control, pipeline pressure regulation, burner management。
Power Generation: Turbine/generator actuator control, boiler feedwater valve modulation, SIL3 interlocks。
Chemical/Refining: Reactor temperature/pressure control, distillation column valve positioning。
Industrial Automation: Critical process control loops requiring SIL3 compliance and high accuracy。
Get a Quote