TRICONEX 8311 Power Supply Module
Description
Model Interpretation
8311
8311: 24VDC input power module, rated 150W
Common part number: 3000606‑100
Related series: 8310(120VAC/DC), 8311(24VDC), 8312(230VAC)
Compatible rack: 8110,8111,8112
Technical Parameters
Electrical Specifications
Input range: 20VDC ~ 30VDC nominal 24VDC
Rated output power: 150W
Main output: 6.5VDC regulated for backplane
Max output current: 23A
Redundancy: 1oo2 dual redundant configuration; single unit can carry full chassis load
Hold‑up time: ≥20ms under nominal input drop to zero
Mechanical Data
Slot occupation: occupies two standard slots inside Tricon chassis
Weight: approx 3.5kg
Mounting: plug‑in backplane installation
Environmental
Operating temperature: −40°C ~ +70°C
Storage temperature: −55°C ~ +85°C
Relative humidity: 5%~95% non‑condensing
Certifications: SIL3 per IEC61508, TÜV, UL, ATEX/IECEx
Indicator & Protection
Front panel LED: PASS, FAULT, OVERTEMP, ALARM
Built‑in protection: overvoltage, overcurrent, short circuit, over temperature shutdown
Full diagnostic data reported to system for fault logging
Core Functions
Convert industrial 24VDC field power into stable internal working voltage for entire rack backplane.
Hot swappable, replace faulty module online without system shutdown.
Dual redundant arrangement improves system availability for safety interlock loop.
Continuous self‑diagnosis and real‑time fault indication for maintenance convenience.
Applications
Oil & gas ESD and F&GS safety system with site standard 24VDC power distribution.
Power plant turbine, boiler safety protection system.
Chemical & refinery reactor, pressure vessel SIL3 interlock system.
Field remote I/O cabinets using local 24VDC power supply.
Get a Quote