Product Description The TRICONEX 8310 is a 175W high‑integrity TMR power supply for Tricon v9–v11 SIS (Safety Instrumented Systems). It provides regulated DC power to the backplane of main (8110), expansion (8111), and remote (8112) chassis, supporting processors and I/O modules in safety‑critical applications. Dual‑module redundancy (1oo2) ensures no single‑point failure for system power.

Description

Model Interpretation

8310

8310: Tricon 120 VAC/VDC Power Module (175W)

Common P/N: 8310 3000605‑100

Family: 8310 (120V), 8311 (24VDC), 8312 (230VAC)

Compatibility: Tricon v9–v11 chassis (8110/8111/8112)

Technical Parameters

Electrical

Input Voltage: 120 VAC/VDC (AC: 85–140 V, 47–63 Hz; DC: 95–180 V)

Output: 6.5 VDC ±1%, 27 A max (175W @ 60°C)

Hold Time: ≥20 ms (nominal to 0V)

Fuse: 5A time‑delay

Redundancy: Dual‑module 1oo2 (one module powers full chassis)

Mechanical

Dimensions (W×H×D): 483 × 362 × 178 mm (19” rack)

Weight: 3.8 kg

Mounting: Slot‑mount in Tricon chassis (2 slots per chassis)

Environmental

Operating Temp: −40°C to +70°C

Storage Temp: −55°C to +85°C

Humidity: 5%–95% RH, non‑condensing

Over‑Temp Trip: 83°C

Certifications: SIL 3 (IEC 61508), TÜV, ATEX, IECEx, UL

Diagnostics & Indicators

LEDs: PASS, FAULT, ALARM, TEMP, BAT LOW

Monitoring: Input voltage, output voltage, current, temperature, battery status

Protection: Overvoltage, overcurrent, short‑circuit, overtemperature

Core Functions

TMR Power Integrity: Delivers clean, regulated power to TMR backplane; supports 2oo3 voting logic.

Redundant Operation: Dual 8310 modules per chassis; either powers full load, no single‑point failure.

Wide‑Range Input: Accepts 120 VAC or DC, adapting to industrial power conditions.

Comprehensive Diagnostics: Real‑time health monitoring with LED status and fault logging.

Hot‑Swap: Online replacement without system shutdown; maintains power during swap.

Applications

Oil & Gas: ESD, F&GS, pipeline safety systems (8110/8111/8112 chassis).

Power Generation: Turbine/boiler protection, generator trip systems.

Chemical/Refining: Reactor safety, pressure/temperature control (SIL 3).

Heavy Industry: Furnace safety, large machine interlocks.