Description
Model Interpretation
8112
8112: Tricon Remote Expansion Chassis (RXM, v9–v11)
Common P/N: 8112 3000604‑100
System Compatibility: Tricon v9.0–v11.x; pairs with 8110 main chassis and 8111 local expansion chassis
Technical Parameters
Mechanical
Form Factor: 19” rack‑mount remote chassis
Dimensions (W×H×D): 483 × 362 × 178 mm
Weight: 23 kg
Slots: 6 logical slots for I/O/communication modules
I/O Bus: Two sets of triplicated RS‑485 ports (375 kbps)
Electrical
Power: Dual redundant power supplies (100–240 VAC, 50/60 Hz)
Power Consumption: ~150 W
Isolation: 2500 Vrms between channels and backplane
Remote Distance: Up to 12 km from main chassis (via SRXM modules)
Environmental
Operating Temp: −40°C to +70°C
Storage Temp: −55°C to +85°C
Humidity: 5%–95% RH, non‑condensing
Certifications: SIL 3 (IEC 61508), ATEX, IECEx, UL
Compatibility
Main Chassis: 8110 (v9–v11)
Local Expansion: 8111 (≤30 m from main)
I/O Modules: Tricon 8xxx series (DI/DO/AI/AO/comms)
Max System: 1 main + up to 14 expansion/remote chassis; total 118 modules
Core Functions
TMR Fault Tolerance: Triple‑modular redundancy with 2‑out‑of‑3 voting; no single‑point failure, same as main chassis。
Remote I/O Extension: Extends I/O to 12 km from main chassis, ideal for large plants with distributed field devices。
Redundant Communication: Triplicated RS‑485 bus ensures fault‑tolerant data transmission between main and remote chassis。
Hot‑Swap & Diagnostics: Online module replacement; comprehensive self‑diagnostics with ≤40 ms SOE resolution。
Cost‑Effective Wiring: Reduces long‑distance field wiring, lowers costs and improves signal integrity。
Applications
Oil & Gas: Offshore platforms, remote wellheads, and large refineries with distributed ESD/F&GS。
Power Generation: Large thermal/hydro power plants with remote turbine/boiler monitoring。
Chemical/Refining: Complex plants with widely spaced reactors, furnaces, and storage tanks。
Heavy Industry: Large steel mills, cement plants, and mining operations with distributed safety interlocks。