330100-90-02
Description
Function Overview
Electromagnetic Eddy Current Signal Conditioning: Provides high-frequency excitation to the probe, outputting a voltage proportional to the clearance
Monitoring Object: Shaft vibration, shaft displacement, eccentricity, keyway signal
Compatible Probe: 3300 XL 8mm probe (e.g. 330101 series)
Electrical Parameters
Power Supply: -17.5 ~ -26 VDC (typical -24 VDC)
Sensitivity: 7.87 V/mm (200 mV/mil)
Linear Range: 0.25 ~ 2.3 mm
Frequency Response: 0 ~ 10 kHz
System Impedance: 50 Ω
Power Consumption: Approximately 12 mA @ -24 VDC
Mechanical and Environmental
Shell: Stainless steel, IP67
Operating Temperature: -40°C ~ +85°C
Weight: Approximately 0.29 kg
Matching Components
Probe: 330101-xx-xx-xx-02-00 (8mm, ClickLoc connector)
Extension Cable: 330130 series (length matched)
Monitoring Module: 3500/40 (vibration), 3500/42 (displacement) Certification
CE, RoHS (without SIL2/3) Application
Steam turbine, compressor, generator and other rotating machinery TSI protection system
Get a Quote