330180-12-05
Description
I. Model Meaning (330180-12-05)
330180: 3300 XL 8mm Eddy Current Preprocessor (General Type) twelve
1: Total system length: 1m (probe + cable)
2: No installation hardware (bare unit, without panel / DIN mounting components)
05: ATEX/IECEx/CSA explosion-proof certification (Ex ia IIC T5)
II. Electrical parameters (same as 330180 series standard)
Power supply: -17.5 ~ -26 VDC (without safety barrier); -23 ~ -26 VDC (with safety barrier)
Current: ≤ 12 mA
Sensitivity: 7.87 mV/μm (200 mV/mil)
Linear range: 0.25 ~ 2.3 mm; recommended gap 1.27 mm (-9 VDC)
Frequency response: 0 ~ 10 kHz
Output impedance: 50 Ω
III. Mechanical and environmental
Size (H×W×D): 63.5 × 61 × 81.3 mm
Weight: approximately 0.32 kg
Shell: A308 aluminum alloy, IP54
Temperature: -35°C ~ +85°C
Certification: ATEX, IECEx, CSA, CE, RoHS, SIL2/3
IV. 1m system kit
Probe: 330191-00-26-01-00 (8mm, 1m integrated cable, explosion-proof)
Extension cable: not required (1m integrated)
Monitor: 3500/40 (vibration), 3500/42 (axial position)
V. Terminal blocks (bare unit terminals definition)
-24 VDC (power negative)
COM (common terminal)
OUT (signal output)
SHIELD (shielding layer)
VI. Differences from 330180-50-05/50-00
330180-12-05: 1m system, no installation accessories, explosion-proof
330180-50-05: 5m system, panel installation, explosion-proof
330180-50-00: 5m system, panel installation, non-explosion-proof
VII. Installation points
Additional purchase of panel mounting base (330180-01) or DIN rail base (330180-02) is required
Gap setting: 1.27 mm (-9 VDC), adjust by measuring COM–OUT voltage with a multimeter
Cable: bending radius ≥ 25mm,严禁 cutting; single end of shielding layer grounded at the cabinet end
Get a Quote