330180-50-00
Description
I. Model Explanation (330180-50-00)
330180: 3300 XL 8mm Eddy Current Preprocessor (API 670) 50
5: Total system length 5m (probe + cable)
0: Panel mounting
00: No explosion-proof certification (non-explosion-proof type, for ordinary industrial environment)
II. Core electrical parameters
Power supply: -17.5 ~ -26 VDC (without safety barrier)
Working current: ≤ 12 mA
Sensitivity: 7.87 mV/μm (200 mV/mil)
Linear range: 0.25 ~ 2.3 mm; recommended gap 1.27 mm (-9 VDC)
Frequency response: 0 ~ 10 kHz (+0/-3 dB)
Output: Negative DC voltage (static displacement + dynamic vibration)
Impedance: 50Ω (full range matched)
III. Mechanical and environmental
Dimensions (H×W×D): 63.5 × 61 × 81.3 mm
Weight: Approximately 0.32 kg
Shell: A308 aluminum alloy, protection IP54
Operating temperature: -40°C ~ +85°C
Certifications: CE, RoHS, SIL2/3 (without ATEX/IECEx/CSA explosion-proof)
IV. 5m system kit
Probe: 330191-00-26-05-00 (8mm, 5m integrated cable, non-explosion-proof)
Extension cable: Not required (5m integrated probe cable)
Monitor: 3500/40 (vibration), 3500/42 (axial position)
V. Terminal connections (panel type)
-24 VDC (power negative)
COM (common terminal)
OUT (signal output)
SHIELD (shielding layer)
VI. Installation points
Panel hole opening: 4 holes for fixed installation, compatible with the old model 3300
Gap setting: 1.27 mm (-9 VDC), adjust by measuring the voltage between COM and OUT with a multimeter
Cable: bending radius ≥ 25mm,严禁 cutting; shield layer grounded at one end of the cabinet
VII. Difference from 330180-50-00
330180-50-00: Ordinary type, no explosion-proof, used in non-hazardous areas
330180-50-05: Explosion-proof type (ATEX/IECEx/CSA), used in Zone 0/1/2 hazardous areas
Get a Quote