330180-50-05
Description
I. Model Explanation (330180-50-05)
330180: 3300 XL 8mm Eddy Current Preprocessor (50Ω, API 670) 50
5: Total system length 5m (probe + extension cable)
0: Panel installation (Panel Mount)
05: With CSA/ATEX/IECEx explosion-proof certification (Ex ia IIC T5)
II. Core technical parameters Electrical
System impedance: 50Ω (full match)
Power supply: -17.5 ~ -26 VDC (without safety barrier); -23 ~ -26 VDC (with safety barrier)
Working current: ≤ 12 mA
Sensitivity: 7.87 mV/μm (200 mV/mil)
Linear range: 0.25 ~ 2.3 mm; recommended gap 1.27 mm (-9 VDC)
Frequency response: 0 ~ 10 kHz (+0/-3 dB)
Output: Negative DC voltage (static displacement + dynamic vibration)
Mechanical and environmental
Installation method: Four-hole mounting on panel (compatible with old model 3300)
Size (H×W×D): 63.5 × 61 × 81.3 mm
Weight: Approximately 0.32 kg
Shell: A308 aluminum alloy, protection IP54
Operating temperature: -35°C ~ +85°C
Certifications: ATEX, IECEx, CSA, CE, RoHS, SIL2/3
III. System Accessories (5m)
Probe: 330191-00-26-05-00 (8mm, 5m integrated cable, explosion-proof)
Extension cable: Not required (5m integrated probe cable)
Monitor: 3500/40 (vibration), 3500/42 (axial position)
IV. Terminal Blocks (Panel Type)
-24 VDC (power negative)
COM (common terminal)
OUT (signal output)
SHIELD (shielding layer)
V. Installation and Gap Setting
Panel hole: 4 holes, spacing consistent with old model 3300
Gap target: 1.27 mm (-9 VDC)
Setting: Use multimeter to measure COM–OUT voltage, fine-tune the probe to the target and lock it
Cable: bending radius ≥ 25mm,严禁 cutting; shield layer grounded at single end of cabinet
VI. Difference from 330180-51-05
330180-50-05: Panel installation, fixed on control panel opening
330180-51-05: DIN rail installation (35mm)
Get a Quote