330180-51-00
Description
I. Model Decoding
330180: 3300 XL 8mm Eddy Current Preprocessor (50Ω system, API 670) 51
5: Total system length: 5m (probe + extension cable)
1: DIN rail installation (35mm standard rail)
00: Standard type, no explosion-proof / safety certification (for general areas)
II. Technical Specifications (Electrical / Environmental / Mechanical)
Electrical Parameters
System Impedance: 50Ω (fully matched, cannot be mixed with 75Ω)
Power Supply Voltage: -17.5 ~ -26 VDC (typical - 24 VDC)
Operating Current: ≤ 12 mA
Sensitivity: 7.87 mV/μm (200 mV/mil)
Linear Range: 0.25 ~ 2.3 mm (10 ~ 90 mils)
Recommended Gap: 1.27 mm (50 mils, approximately - 9 VDC)
Frequency Response: 0 ~ 10 kHz (+0/-3 dB)
Output Signal: Negative DC Voltage (static displacement + dynamic vibration)
Signal Transmission Distance: Up to 305m from Preamplifier to Monitor
Environmental and Mechanical
Operating Temperature: -35°C ~ +85°C
Storage Temperature: -51°C ~ +100°C
Installation Method: 35mm DIN Rail Snap-In Installation (with electrical isolation included)
Dimensions: 81.3 × 35.1 × 63.5 mm
Weight: Approximately 0.25 kg
Shell: A308 Aluminum Alloy, Protection IP54
Certifications: CE, RoHS (No explosion-proof, No SIL)
III. Standard Accessories (5m System)
Probe: 330191-00-26-05-00 (8mm, 5m integrated cable, standard temperature)
Extension Cable: Not Required (5m integrated probe cable)
Monitor: 3500/40 (Vibration), 3500/42 (Axial Position)
IV. Installation and Wiring
1. Rail Installation
Align with 35mm DIN Rail, press down to secure; base comes with insulation, no additional insulation board required
2. Wiring Terminal (Standard)
-24 VDC (Power Negative)
COM (Common Port)
OUT (Signal Output)
SHIELD (Shielding Layer)
3. Gap Setting
Objective: 1.27 mm (-9 VDC)
Measure COM–OUT voltage with a multimeter, fine-tune the probe to the target and lock it
4. Cable and Shielding
Bend radius ≥ 25mm, do not cut
Shielding: Single-ended grounding at the cabinet end, floating at the probe end
V. Calibration (Periodic 12 Months)
Use standard gap blocks: 0.25/1.27/2.3 mm
Sensitivity Error: ≤ ±1%; Linear Deviation: ≤ ±0.31 mm
VI. Difference from 330180-51-05
330180-51-00: Standard Type, No Explosion-proof, for ordinary industrial environments
330180-51-05: With CSA/ATEX/IECEx Explosion-proof Certification, for Hazardous Areas
Get a Quote