Model: 330180-X2-00 Brand: Bently Nevada Category: 3300 XL 8mm ETR High Temperature Preamplifier (Proximitor) Features: 50Ω, DIN rail, ETR high temperature, system length 0m (probe directly connected)

Description

Model Breakdown Explanation (330180-X2-00)

330180: 3300 XL 8mm Eddy Current Preamplifier (50Ω) X2

X: ETR High Temperature Version (Suitable for -55℃ to +232℃ probes)

2: DIN Rail Installation (No panel accessories included)

00: System Length 0m (The probe comes with its own cable directly connected to the preamplifier, without extension cable)

Core Parameters (Consistent with X2-05, only the length is different)

Compatible Probe: 330191 Series 8mm ETR High Temperature Probe (50Ω)

Compatible Extension Cable: 330190 Series (50Ω, this model does not need it)

System Impedance: 50Ω (Must be fully matched throughout)

Power Supply: -17.5 to -26VDC (Typical -24VDC, ≤12mA)

Sensitivity: 7.87mV/μm (200mV/mil)

Linear Range: 0.25 to 2.3mm

Frequency Response: 0 to 10kHz

Operating Temperature: -55℃ to +232℃ (ETR High Temperature Grade)

Output: Negative voltage proportional to the clearance (static + dynamic)

Appearance: Blue cast shell, DIN Rail-mounted

Size: Approximately 81×35×58mm; Weight approximately 0.25kg

Typical Accessories (0m system, no extension cable)

Probe: 330191-00-26-00-00 (comes with 0m cable, direct connection)

Preamplifier: 330180-X2-00

Monitoring Module: 3500/40 (Axial Vibration), 3500/42 (Axial Displacement) Application scenario

The installation point of the probe is very close to the cabinet (within 1m), and no extension cables are required.

Short-distance vibration/ displacement monitoring in the high-temperature area of gas / steam turbines

Monitoring of high-temperature equipment with limited space and the requirement for simple wiring

Installation points

A complete 50Ω matching must be used: 75Ω/300Ω systems must not be mixed

The probe is directly connected to the preamplifier, and no extension cables can be added (the model is defined as 0m)

The recommended gap is 1.27mm (50mil)

The cables must not be cut or severely bent; keep away from power / frequency conversion cables

The shield layer should be grounded at one end on the control cabinet side