1. General Description
The CI801 is a high‑performance, configurable fieldbus communication interface (FCI) that connects the ABB S800 I/O system to a PROFIBUS DP‑V1 network. It acts as a PROFIBUS slave, enabling data exchange between S800 I/O modules and PROFIBUS DP masters (e.g., ABB AC 800M controllers, third‑party PLCs/DCS).
Key functions:
Signal processing and data acquisition from S800 I/O modules
Supervision and diagnostic data collection
Hot Configuration In Run (HCIR) – online I/O module configuration without stopping the system
HART pass‑through – transparent communication with HART‑compatible field devices
I/O module configuration and parameterization
Included in delivery:
1 × CI801 module
1 × power supply connector
1 × TB807 modulebus terminator
2. Technical Specifications
2.1 Communication
Protocol: PROFIBUS DP‑V1 (slave)
Baud rate: Up to 12 Mbit/s (12,000 kbit/s)
Connector: 1 × D‑sub 9‑pin (PROFIBUS)
Modulebus: S800 internal modulebus (backplane)
2.2 Electrical
Supply voltage: 24 VDC (nominal)
Current consumption: 140 mA (typical)
2.3 Environmental
Operating temperature: 0 °C to +55 °C
Storage temperature: −40 °C to +70 °C
Relative humidity: 5 % to 95 %, non‑condensing
Pollution degree: Degree 2 (IEC 60664‑1)
Corrosion protection: ISA‑S71.04 G3
Protection class: IP20 (EN 60529)
2.4 Mechanical
Dimensions (H × W × D): 136 × 85.8 × 58.5 mm
Weight: 0.34 kg
3. Compatibility
System: ABB 800xA, Compact Product Suite (S800 I/O)
Controller: AC 800M (as PROFIBUS DP master)
I/O modules: Most S800 I/O modules; excludes: DI830, DI831, DI885, AI880, DI880, DO880 (basic firmware)
4. Installation & Wiring
Mounting: Snap onto S800 I/O rack (DIN rail or panel mount)
Power: Connect 24 VDC to the power connector
PROFIBUS: Connect D‑sub 9‑pin to PROFIBUS DP network; use standard PROFIBUS cable
Termination: Ensure PROFIBUS line termination is correct (activated at both ends of the bus)
Modulebus: The CI801 connects automatically to the S800 backplane when inserted into the rack
5. Configuration
Use ABB Control Builder M (for AC 800M) or 800xA Engineering software
Configure as a PROFIBUS DP slave
Set PROFIBUS address, baud rate, and I/O data mapping
Enable HCIR and HART pass‑through as required
6. Operation & Maintenance
LED indicators:
RUN: Module power and operation status
COM: PROFIBUS communication activity
ERR: Fault indication (e.g., communication error, module fault)
Hot swap: Module can be replaced online without system shutdown
Firmware update: Supported via PROFIBUS or S800 modulebus
7. Safety & Standards
Certifications: CE, UL, cUL
Compliance: EN 61000‑6‑2 (EMC), EN 61158 (PROFIBUS)
8. Ordering Information
Order no.: 3BSE022366R1
Description: CI801 PROFIBUS DP‑V1 Communication Interface, S800 I/O


Get a Quote