CFP-CB-3
Description
I. Basic Information
Model: CFP-CB-3 (cFP-CB-3)
Manufacturer: National Instruments (NI)
Series: Compact FieldPoint (cFP)
Part Number: 778618-03
Status: Obsolete
Location: Specialized for high-precision thermocouple measurement, isothermal structure reduces terminal temperature difference
Core Application: Combined with cFP-TC-120 / TC-125 (16-channel thermocouple input)
II. Key Differences from CFP-CB-1 (Most Frequently Asked Questions) Table
Parameters:
CFP-1 (General type) - 36-pin (common for all modules)
CFP-3 (Isothermal thermocouple type) - 18-pin (only for thermocouple module)
Structure: Standard plastic casing
CJC accuracy: ±0.15~0.3 °C
±0.05~0.1 °C (higher)
Temperature gradient: Normal (with temperature difference between terminals)
Extremely small (terminal isothermal, lower thermal error of thermocouple)
Recommended modules: AI-100/102/111, AO, DI/DO
Only cFP-TC-120 / TC-125
Price: Lower
Higher (high-precision thermocouple dedicated)
One sentence: CB-1 general; CB-3 high-precision dedicated for thermocouples, isothermal + more accurate CJC.
III. Core Specifications (Electrical / Wiring)
Number of terminals: 18 screw terminals (compatible with 16 thermocouples + power / ground)
CJC sensor: Built-in high-precision thermistor, cold junction compensation accuracy ±0.05~0.1 °C
Isothermal design: Temperature is uniform in I/O terminal area, suppressing mV level error of thermocouple
Rated voltage: 250 Vrms (isolated)
Rated current:
V/C power terminal: 4 A
Signal terminal: 2 A
Wiring specification: 16–26 AWG copper wire, stripped 6 mm, torque 0.5–0.6 N·m
Protection: Short circuit / Overcurrent protection, LED diagnosis
IV. Mechanics and Environment
Size: 127 × 66 × 24 mm (same as cFP standard module)
Weight: Approximately 110 g
Installation: cFP-BP-4 / BP-8 backplate, hot-swappable
Operating temperature: -40 °C ~ +70 °C
Humidity: 10%–90% RH, no condensation
Protection: IP20, double stress release rods + belt slot (anti-vibration)
V. Compatibility and Recommended Combinations
The only recommended module: cFP-TC-120 (16 thermocouples, J/K/T/E/R/S/B/N)
Compatible backplates: cFP-BP-4, cFP-BP-8
Not recommended for: AI-100/102/111, AO-200/210, DI/DO (terminal insufficient, not isothermal)
VI. Retirement Replacement
Original system: Direct replacement with the same model spare parts (high-precision thermocouple measurement is necessary)
New system:
Module: NI-9213 (C series, 16 thermocouples, ±0.05 °C CJC)
Base: NI-9923 (Isothermal type, high-precision CJC)