cFP-2200
May 15, 2026

cFP-2200

I. Basic Information Model: cFP-2200 Part Number: 777317-2200 Series: Compact FieldPoint (cFP-22xx High-Performance Generation) Position: High-speed single-core, basic real-time control, data recording, economical gateway

Description

I. Basic Information

Model: cFP-2200

Part Number: 777317-2200

Series: Compact FieldPoint (cFP-22xx High-Performance Generation)

Position: High-speed single-core, basic real-time control, data recording, economical gateway

II. Hardware Specifications (Key Point, Compared with 2120)

Processor: 400 MHz Real-time CPU (VxWorks) → Approximately 2.1 times faster than the 188 MHz of the 21xx series Memory:

DRAM: 128 MB (same as 2110/2120)

Non-volatile storage: 128 MB built-in (same as 2120, twice the size of 2100/2110)

Communication interface:

Ethernet: 1 × 10/100 Mbps RJ45 (TCP/IP, Modbus TCP)

Serial port: 1 × RS-232 (DB9) (same as 2100; 2210 has 2 × RS-232; 2220 has 3 × RS-232 + 1 × RS-485)

I/O expansion: cFP-BP-4 / BP-8 backplane, up to 8 cFP I/O modules

Storage expansion: CompactFlash card + 1 × USB port (program / data recording / USB upgrade)

Power supply: 11–30 VDC industrial wide voltage, supports dual redundant input

Temperature range: -40 °C ~ +70 °C (industrial wide temperature)

Size / Weight: 127 × 102 × 51 mm, approximately 0.28 kg

DIP switch: 6 (IP reset, safe mode, user-defined, etc.)

III. Comparison of cFP-2120 / 2200 / 2210 / 2220 cores Table

Project  cFP-2120  cFP-2200  cFP-2210  cFP-2220 (Top Configuration) CPU 188 MHz 400 MHz 400 MHz 400 MHz

DRAM 128 MB 128 MB 256 MB 256 MB

Built-in storage: 128 MB, 128 MB, 128 MB, 256 MB

Ethernet: 1 port, 1 port, 1 port, 2 ports (redundant)

Serial ports: 3×RS-232 + 1×RS-485, 1×RS-232, 2×RS-232, 3×RS-232 + 1×RS-485

USB: None, 1 port, 1 port, 1 port

Typical applications: Multi-serial bus, High-speed basic control, High-speed dual serial ports, High-speed multi-serial ports + redundancy

IV. Software and Protocols

Real-time system: LabVIEW Real-Time (VxWorks)

Programming: LabVIEW (recommended), LabWindows/CVI

Supported protocols:

Ethernet: Modbus TCP, NI Real-Time Network, TCP/IP

Serial ports: Modbus ASCII/RTU, Optomux

Driver requirements: NI-FieldPoint 6.0.1+, LabVIEW RT 8.5.1+

V. Typical Applications

High-speed real-time control: Multi-loop PID, High-speed data acquisition, Complex algorithms (2 times faster than 21xx)

Medium-sized data recording: 128 MB memory + 128 MB storage + CF card expansion

Single serial port device networking: 1 RS-232 instrument/PLC connected to Ethernet

Distributed I/O master station: Remote high-density analog/digital quantity acquisition

NI3.jpg