Z7138
Description
I. Model Positioning (Easy Differentiation within the Same Series)
Z7116: 16DI (24VDC Input)
Z7126: 16AI (4-20mA Input)
Z7127: 16AO (4-20mA Output)
Z7136: 16DO (Relay Type, 250VAC/2A)
Z7138: 8DO (Transistor Type, 24VDC/2A) ✅
Series: H41q/H51q (Old System); X-Series (HIMax) Not Available
II. Basic Information
Brand: HIMA
Model: Z7138
Type: 8-channel safety-level digital output DO (transistor / 24VDC)
Safety Level: SIL3 (IEC 61508), TÜV AK6, PL e
Output Type: 24VDC transistor output (source type / sinking option available)
Load: 24VDC DC load (valve, contactor, alarm light)
Adapter Backplane: H41q/H51q rack (not X-BASE)
Status: Older model original, replaceable spare parts available
III. Core Technical Parameters (Official)
Channels: 8 DO channels, isolated independently
Output Voltage: 24VDC (±10%)
Current per channel: ≤2A (resistive), ≤1A (inductive)
Maximum load: 48W per channel (24V x 2A)
Short circuit / overload protection: electronic self-recovery, SIL3 diagnosis
Isolation: 500V AC isolation between channels
Diagnosis: Output short circuit / open circuit / overload / power supply failure, diagnostic coverage ≥ 99.9%
Power supply: 5VDC (backplane) + 24VDC (field load)
Power consumption: ≈8W
Operating temperature: -20℃ to +70℃
Size: Standard 8TE (same as Z7116/Z7126/Z7127/Z7136)
Weight: ≈0.5kg
IV. Derivative Model Rules (Same Series Standards)
Z7138/3330: Bare module (without cables)
Z7138/3330/C5: C5 anti-corrosion coating (for marine / chemical corrosion environments)
Z7138/3331: With 5-meter prefabricated shielded cable + connector
V. Z7138 vs Z7136 (Selection Key) Table
Comparison item Z7138 (8DO Transistor) Z7136 (16DO Relay)
Number of channels 8 channels
Output type 24VDC Transistor (DC) Relay contacts (AC/DC compatible)
Voltage range Only 24VDC 24VDC - 250VAC
Single-channel current 2A (24VDC) 2A (resistive) / 1A (inductive)
Life Semi-permanent (no mechanical contacts) Approximately 100,000 times (full load)
Applicable loads 24VDC Electromagnetic Valves, Warning Lights AC/DC Electromagnetic Valves, Contactors, Motors
Price Slightly higher Slightly lower
Six. Typical Applications (SIS/ESD/F&G Systems)
24VDC Electromagnetic Valve Drive: Emergency Shut-off Valve, Blow-off Valve, Fire Valve
Safety Relay / Contactor: Pump / Fan / Compressor Safety Shutdown
Alarm Output: 24VDC Sound and Light Alarm, Warning Light
Interlock Contacts: DCS/PLC 24VDC Interlock Signal
Seven. Compatibility (Must Read)
✅ Compatible: H41q / H51q / HIQuad X Older Systems
❌ Incompatible: HIMax X Series (X-CPU01/X-SB01), Completely Incompatible

Get a Quote