F8628X
Description
Part Code Definition
F8628: base PROFIBUS DP communication model; X denotes revised upgraded hardware edition; PN 984862865 is fixed factory production coding。
Technical Specifications
Power supply:24VDC(18~32VDC), typical power consumption 5W
Form factor:3U×4TE Eurocard plug-in card for 19-inch standard rack, weight≈160g
Operating environment:-25℃~+70℃,5%~95%RH non-condensing,IP20 protection
Safety certification:TÜV SIL3(IEC61508/IEC61511),Cat.4 EN954,PL e ISO13849,CE certified
Firmware requirement:compatible with OS41q/51q V7.0-7 and above system firmware
Interface & Communication Configuration
Front panel ports
1×DB9 9PIN:PROFIBUS-DP slave interface, standard PROFIBUS wiring
1×RJ45 10/100Mbps Ethernet:for ELOP II online program download & local diagnosis
1×RJ12 HSR high-speed redundant bus port:for rack internal redundant interconnection with BV7053 cable
6pcs status LED +2 DIP switch:module address & function setup
Backplane:private HIMA safety bus connecting rack CPU(F8650X) and rack I/O modules
Supported protocols:PROFIBUS-DP Slave,Modbus TCP,ELOP II Ethernet download protocol,config via HK-COM-3 system function block
Core Functions
Real-time safety data interaction between HIMA SIS system and third-party DCS/PLC via PROFIBUS DP bus, online program upload/download & fault diagnosis through onboard Ethernet by ELOP II/SILworX,HSR redundant rack interconnection for master-slave CPU data sync,continuous module self-diagnosis & communication fault alarm feedback to upper CPU/DCS。
Application Scenarios
Petrochemical SIS/ESD system PROFIBUS networking,boiler BMS safety system connecting DCS via DP bus,gas turbine safety interlock data transmission,chemical plant F&G fire&gas system communication expansion,offshore platform safety cabinet PROFIBUS bus integration。
Operation & Maintenance Notes
Forbid hot plug under powered rack in critical safety loop;use shielded PROFIBUS cable for DP wiring with terminal matching bus terminator;Ethernet port adopt CAT5E shielded cable;set DIP switch address before power on;only configure communication parameters with certified ELOP II V4.1+ software。
Get a Quote