X-CPU01
Description
HIMA X-CPU-01 (HIMax System Core CPU, SIL3)
X-CPU-01 is the central processing unit (CPU) of the German HIMA HIMax (X series) safety instrumented system (SIS). The entire unit is SIL3 certified, 1oo2 redundant, and hot-swappable. It is responsible for executing safety logic, I/O scheduling, redundant switching, and safety communication. It is the core of safety systems such as ESD/BMS/FGS.
1. Basic Information
Model: X-CPU-01 (X-CPU01, Order Number: 940781)
Brand: HIMA (Black Horse)
Series: HIMax (X series)
Type: Safety CPU Module (1oo2 Redundancy)
Safety Level: IEC 61508 / IEC 61511 SIL3 (TÜV Certification)
Status: Brand new original, in stock, supports hot-swapping
Adapter Backplane: X-BASE-PLATE-10/15/18-01
Matching Connector Board: X-CB-001-01 (Including 4-port Ethernet Switch)
II. Hardware Core Parameters
Processor: Dual-core ARM Cortex-A53 / PowerPC (1oo2 Security Architecture) Memory:
Flash: 256 MB (program / event storage)
DRAM: 128 MB
NVRAM: Built-in (power-on data retention)
Program capacity: 1023 kB per user program, supports 32 parallel safety programs
Power supply: 24 VDC (‑15% ~ +20%), typical power consumption ≈ 15 W, current 1.4 A
Size (width × height × depth): 29.2 mm × 236 mm × 310 mm (19-inch rack slot)
Weight: ≈ 1.3 kg
Protection: IP20 (in cabinet)
Environment:
Operating temperature: –20 ℃ ~ +60 ℃
Storage temperature: –40 ℃ ~ +85 ℃
Humidity: 5%–95% without condensation
III. Redundancy and Safety (Critical)
Architecture: 1oo2 (two-out-of-one) hardware redundancy, dual-core interlocked self-check
Redundancy switching: Automatic non-disruptive switching, time < 50 ms, single failure does not affect operation
Safety mechanism:
Hardware-level mandatory fail-safe (Fail-Safe)
Comprehensive self-check + mutual check (period < 10 ms)
Fault automatic transition to safe state and record events
Authentication: SIL3, Cat.4, PL e (EN 954‑1 / ISO 13849‑1)
IV. Communication Interfaces (X‑CB‑001‑01 Connector Board)
Ethernet: 4 × 10/100/1000 Mbps (secure Ethernet SafeEthernet)
Protocols: Modbus TCP, PROFIBUS DP, SafeEthernet, TCP/IP
Serial ports: RS‑232 / RS‑485 (optional, for debugging / third-party communication)
System bus: Backplane high-speed safety bus (automatically connects I/O and power)
Redundant communication: Supports CPU redundancy + network redundancy, no single point of failure
V. Function Overview
Safety logic execution: Runs SIL3 safety programs such as ESD/BMS/FGS, supports ladder diagram / function block / structured text (ST)
I/O control: Manages the entire I/O modules (X‑AI‑01, X‑DI‑01, etc.), hot-swappable identification and configuration
Redundancy management: Dual CPU synchronous operation, data comparison, fault switching, throughout without disturbance
Events and diagnostics: Records CPU/I/O/communication events (timestamp ms level), supports online diagnosis and fault traceability
System monitoring: Real-time monitoring of power, fan, temperature, bus status, abnormal alarm and upload to the upper computer
VI. Typical Configuration (Required)
CPU: X‑CPU‑01 ×2 (1oo2 redundancy)
Backplane: X‑BASE‑PLATE‑18‑01 (18 slots)
Power supply: PS2000/230 ×2 (redundant)
Fans: K9203A ×2 (hot-swappable)
Connector board: X‑CB‑001‑01 ×2 (with CPU)
VII. Differences from Older Models (H41q/H51q) CPUs
X‑CPU‑01 (HIMax/X series): SIL3, 1oo2, hot-swappable, gigabit Ethernet, 4 network ports, new architecture, in stock
K‑CPU‑01 (H41q/H51q): SIL3, 1oo2, non-hot-swappable, 100 Mbps network, discontinued
VIII. Application Scenarios
Petroleum and Chemical Industry: ESD emergency stop, FGS fire and gas system, BMS combustion management
Electricity: Turbine / boiler protection, generator excitation control
Natural Gas: Long-distance pipeline cut-off, compressor protection Pharmaceuticals / Fine Chemicals: Reaction Vessel Safety Interlock, Explosion Protection

Get a Quote