H7013
Description

H7013 is a SIL3 safety controller from German HIMA, belonging to the HIMax series of core modules. It is equipped with a dual-core ARM Cortex-A53 processor and is used for logical control and I/O management in ESD/BMS/F&G and other safety systems.
1. Basic Information
Model: H7013
Brand: HIMA (Germany)
Type: Safety CPU Controller (Redundant / Single System Option)
Safety Level: SIL3 (IEC 61508/61511), AK6, PL e/Cat.4
Certifications: CE, UL, TÜV, ATEX/IECEx (Zone 2 Explosion-proof)
Installation: 19-inch standard rack, compatible with H41q/H51q/HIMax systems
Environment: IP20; Operating Temperature **-20℃~+60℃**, Storage Temperature -40℃~+85℃
II. Core Parameters
Processor: Dual-core ARM Cortex-A53, with a clock speed of 1GHz
Control Power Supply: 24VDC (±15%), current ≈ 1.5A
System Bus: Dual redundant safety bus (SafeEthernet), rate 100Mbps
Communication Interfaces: 2×RJ45 (Ethernet TCP/IP), RS-485, RS-232
Program Memory: 4GB Flash, 1GB RAM
Response Time: Logical scan ≤ 1ms, I/O response ≤ 10ms
Redundancy Support: Dual CPU redundancy, dual bus redundancy, no single point failure
III. Terminal Definitions (Simplified) Table
Terminal Function
1 +24VDC (Power +)
2 0V (Power -)
3-4 ETH1 (Ethernet 1, redundant bus)
5-6 ETH2 (Ethernet 2, redundant bus) 7 RS‑485+
8 RS‑485‑
9 RS‑232 TX
10 RS‑232 RX
IV. Safety Features
Fault Safety: In the event of power loss / failure, all outputs are forced to a safe state (in accordance with ESD "Power Loss Safety").
Self-Diagnosis: Real-time self-checks for CPU, power supply, bus, and I/O; faults trigger automatic alarms and switch to redundancy.
Redundant Architecture: Supports dual CPU hot backup, dual bus redundancy, with a switching time of ≤ 500ms, and no data loss.
Isolation Design: Electrical isolation between the system side and the field side; isolation withstand voltage ≥ 1500VAC.
V. Installation and Wiring
Installation: Vertical installation of the rack, with a spacing of ≥ 20mm for heat dissipation; away from strong electromagnetic interference, corrosive / dusty environments.
Wiring: Power-off operation, cable ≤ 2.5mm²; separate wiring for power, signal, and communication lines, away from power lines.
Shielding: Double-ended grounding of the communication cable shielding layer to reduce interference; industrial shielded network cable for Ethernet.
VI. Debugging and Maintenance
Power-on Test: Power LED on; bus LED flashing normally; communication with programming software SILworX is normal.
Program Download: Download safety program through SILworX, configure I/O modules (such as H7011, H4137).
Daily Maintenance: Check wiring tightness and no corrosion every 6 months; clean with dry air blowing; back up programs.
Troubleshooting:
Communication Interruption: Check network cable, bus configuration, and redundancy switching → Replace module;
Program Error: Check logic program, I/O configuration → Redownload program;
Power Failure: Check 24VDC input, power module → Replace power supply.
VII. Typical Applications
Petroleum / Chemical: ESD emergency stop system, BMS burner management, F&G fire gas system;
Oil and Gas / Power: Offshore platform safety control, gas turbine / boiler protection, hazardous area valve interlock;
Compatible Systems: HIMax/H41q/H51q series SIS, compatible with H7011 (DO), H4135 (CPU), H4136 (redundant relay).