F8641
Description
F8641 (HIMA High-End CPU Module)
Basic Information
Model: F8641
Brand: HIMA (German High End)
Part Number: 981864102
Product Type: Safety CPU Module (Controller)
Applicable System: H41q/H51q Safety Instrumented System (SIS)
Safety Level: IEC 61508 SIL3, TÜV Certified
Architecture: Triple Redundancy TMR (3-channel CPU)
Installation Method: 19" Rack Slot Type
Protection Level: IP20
Status:停产 (EOL: 2010-03-31), Original stock available.
Hardware Specifications
Processor: 32-bit secure CPU, with a clock frequency of 100 MHz
Memory: 128KB RAM; 1MB Flash (system / user programs)
Processing Capacity: Supports up to 128 I/O points
Size: 25mm × 127mm × 203mm (width × height × depth)
Weight: Approximately 0.4kg
Electrical Parameters
Power Supply: 24VDC (18~32VDC)
Power Consumption: Typical 5W
Backplane Interface: Dedicated system bus, connects I/O modules
Communication Interface
Serial Port: 2×RS232/RS485 (DB9), supports Modbus RTU
Ethernet: 1×RJ45 (10/100Mbps), used for programming / diagnosis
Redundancy Interface: Supports TMR triple redundancy interconnection
Environmental Parameters
Operating Temperature: -20℃ ~ +60℃
Storage Temperature: -40℃ ~ +85℃
Relative Humidity: 5%~95%, no condensation Core function
Safety logical operation: Core control of the SIS system, execution of safety interlock programs such as ESD/BMS/F&G.
Triple redundancy fault tolerance: Three-channel CPUs operate synchronously, faults are automatically voted, and there is no single-point failure.
Hardware self-diagnosis: Diagnostic coverage ≥ 99%, real-time detection of CPU, memory, communication, and I/O failures.
Program download and online diagnosis: Ethernet / serial port connection, supports remote maintenance and fault troubleshooting.
Hot-swappable redundancy: Supports dual CPU redundancy configuration, online replacement without interrupting system operation.
Panel indicator lights
PWR (green): Normal power supply
RUN (green): Normal operation (flashing)

ALM (red): Hardware / program failure
COM (yellow): Communication activity
I/O (yellow): I/O bus status
Installation and maintenance
Push the rack slot in and lock it to ensure reliable contact with the backplane.
Connect 24VDC, Ethernet / serial port, and redundant cables, and ground the cabinet.
Daily inspection indicator lights, regularly tighten terminals, and clean and dust-proof.
Fault replacement: Directly replace the same model F8641, the redundant system automatically synchronizes, and no reconfiguration is required.
Get a Quote