F8628
Description
F8628 / F8628X (HIMA High Performance PROFIBUS DP Communication Module)
Model Relationship
F8628: Basic Edition (Out of production / Available for older models)
F8628X: Enhanced Edition (Current mainstream, directly replacing F8628)
Part Number: F8628X = 984862865
Basic Information (F8628X)
Brand: HIMA (German)
Series: H41q / H51q Safety System
Type: PROFIBUS DP Slave Station + Ethernet Communication Module
Safety Level: IEC 61508 SIL3, TÜV Certified
Installation: 19" Rack, occupies 3HU × 4WU
Protection: IP20
Weight: Approximately 0.5kg
Electrical parameters
Backplane power supply: 5VDC / 1A
System power supply: 24VDC
Power consumption: Typical 5W, maximum 10W
Insulation withstand voltage: Communication port to ground 500V AC / 1min
Protection: Overvoltage, undervoltage, reverse connection, overtemperature, short circuit
Hardware performance
Processor: 32-bit secure communication processor
Memory: 4MB Flash (firmware), 8MB SDRAM (data)
Architecture: TMR triple redundancy, dual bus fault tolerance
Diagnostic coverage: ≥ 99%
Response time: ≤ 10ms (safety data)
Communication interface (F8628X)
PROFIBUS DP: 1 × RS485 (DB9), 12Mbps, slave station
Ethernet: 1 × RJ45, 10/100Mbps (IEEE 802.3)
HSR (redundancy): 1 × RJ12 (interconnected with redundant module)
Debugging port: 1 × RS-232 (DB9, local configuration)
Supported protocols:
F8628: Only PROFIBUS DP
F8628X: PROFIBUS DP + Modbus TCP + ELOP II (Ethernet programming)
Environmental parameters
Operating temperature: -20℃ ~ +60℃
Storage temperature: -40℃ ~ +85℃
Humidity: 5%~95%, no condensation
Vibration / shock: Compliant with IEC 60068
MTBF: > 1,000,000 hours Core function
PROFIBUS DP Slave Station: SIL3 for safety communication, connected to DCS/PLC
Ethernet Programming: ELOP II V4.1+ can download programs via Ethernet
Redundancy and Fault Tolerance: Dual modules / dual link redundancy, automatic fault switching
Protocol Conversion: Seamless interconnection between HIMA system and PROFIBUS devices
Hot Swap: Online replacement, automatic synchronization of configuration
Panel Indicators
PWR (Green): Normal power supply
RUN (Green): Normal operation (flashing)
ALM (Red): Fault alarm
ETH (Yellow): Ethernet transmission and reception
PB (Yellow): PROFIBUS communication
F8628 vs F8628X Differences
F8628: Only PROFIBUS DP; no Ethernet programming; older model
F8628X: PROFIBUS DP + Modbus TCP + ELOP II Ethernet programming; hardware enhancement; can directly replace F8628
Installation and Maintenance
Push the rack slot in and lock it to ensure reliable contact of the backplane
Connect PROFIBUS, Ethernet, and HSR interfaces according to specifications, ground the cabinet
Daily inspection indicator lights, regularly tighten terminals, clean dust
Direct replacement of the same model, no need to reprogram the program

Get a Quote