F7130A
Description
Basic Information
Model: F7130A
Brand: HIMA
Product category: Safety Isolation DC/DC Power Module
Application system: H41q/HIQuad Safety Instrumented System (SIS)
Safety certification: IEC 61508 SIL3, TÜV, ATEX
Part number: 984713060
Installation method: DIN rail installation
Protection level: IP20
Weight: Approximately 1.0 kg
Electrical parameters
Input voltage: 24VDC, allowable fluctuation range -15% to +20%
Input ripple: <15% (rpp)
Recommended input fuse: 5A gL (slow melting type)
Output voltage (CPU/I/O): 5VDC (±0.25V)
Output current (CPU/I/O): Maximum 10A
Output voltage (HIBUS): 5VDC (±0.25V)
Output current (HIBUS): Maximum 1A
Electrical isolation: withstand voltage between input and output is 500V AC
Protection features: overvoltage protection, current limiting protection, short circuit protection, overheat protection
Conversion efficiency: ≥70%
Operating mode: supports dual-module redundant parallel connection Environmental parameters
Operating temperature: -20℃ ~ +60℃
Storage temperature: -40℃ ~ +85℃
Relative humidity: 10% ~ 90%, no condensation
Anti-vibration and shock resistance: Compliant with industrial IEC standards
Core functions
Convert 24VDC to isolated 5VDC, providing power for the CPU, I/O backplane and HIBUS interface of the H41q/HIQuad system
Electrical isolation of input and output, blocking interference
Integrated overvoltage, undervoltage, overcurrent, short circuit and overheating protection, self-protection in case of faults
Independent power supply circuit design, separate power supply for CPU/I/O and HIBUS interface
Panel LED indicators, showing input voltage (L+) and output status
Support for hot swapping, allowing module replacement online
Caution for use
Reserve space for heat dissipation, away from strong interference equipment such as frequency converters and contactors
24V input uses an independent regulated power supply, not connected to high-power loads in the same circuit
The cabinet is reliably grounded, with a grounding resistance of ≤ 4Ω, single-ended grounding of the shielding wire
Ensure consistent output voltage of the two modules during redundant parallel operation to avoid internal circulation
Regularly check terminal fastening, no oxidation, and no condensation
Faults can be directly replaced with the same model without modifying wiring and programs

Get a Quote