F7130
May 14, 2026

F7130

Basic Information Model: F7130 Brand: HIMA Product category: Safety Isolation DC/DC Power Module Application system: H41q/HIQuad Safety Instrumented System (SIS) Safety certification: IEC 61508 SIL3, TÜV, ATEX Installation method: DIN rail installation Protection level: IP20 Weight: Approximately 1.0kg Part number: 981713002

Description

Basic Information

Model: F7130

Brand: HIMA

Product category: Safety Isolated DC/DC Power Module

Application system: H41q/HIQuad Safety Instrumented System (SIS)

Safety certification: IEC 61508 SIL3, TÜV, ATEX

Installation method: DIN rail installation

Protection level: IP20

Weight: Approximately 1.0 kg

Component number: 981713002 

Electrical parameters

Input voltage: 24VDC, allowable fluctuation range -15% ~ +20%

Input ripple: <15% (rpp)

Recommended input fuse: 5A gL (slow melting type)

Output voltage (CPU/I/O): 5VDC (±0.25V)

Output current (CPU/I/O): Maximum 10A

Output voltage (HIBUS): 5VDC (±0.25V)

Electrical isolation: Isolation between input and output

Protection features: Overvoltage protection, current limiting protection, short circuit protection

Conversion efficiency: ≥77%

Operating mode: Supports redundant parallel connection 

Environmental parameters

Operating temperature: -20℃ ~ +60℃

Storage temperature: -40℃ ~ +85℃

Relative humidity: 10% ~ 90%, no condensation

Vibration and shock resistance: Compliant with industrial IEC standards 

Core Function

Convert 24VDC to isolated 5VDC, providing power for the CPU, I/O backplane and HIBUS interface of the H41q/HiQuad system

Electrical isolation of input and output to block interference

Integrated overvoltage, undervoltage, overcurrent and short-circuit protection, with self-protection in case of faults

Independent power supply circuit design, separate power supply for CPU/I/O and HIBUS interface

Panel LED indicators to display input voltage (L+) and output status

Support hot swapping, allowing for online module replacement 

Usage Notes

Ensure there is sufficient cooling space during installation and keep it away from strong interference devices such as frequency converters and contactors.

The 24V input uses an independent voltage stabilizing power supply and is not connected to the same circuit as high-power loads.

The cabinet should be reliably grounded, with a grounding resistance of ≤ 4Ω. The shielded wire should be grounded at one end only.

When redundant parallel operation is performed, ensure that the output voltages of the two modules are consistent to avoid internal circulation.

Regularly check that the terminals are securely fastened, without oxidation or condensation.

In case of a fault, a replacement of the same model can be directly made without the need to modify the wiring or the program.

黑马14.jpg


Get a Quote