F670532
Description
F670532 (Material Number 984670532) is an upgraded replacement version of HIMA F6705: dual-channel SIL3 safety analog output (0/4–20mA), TMR redundancy, and interchangeable directly.
I. Core Parameters (984670532)
Model: F670532 (984670532)
Function: 2 channels of AO, 0–20mA/4–20mA (software selectable)
Safety level: SIL3, AK1~AK6, Cat.4/PL e (TÜV)
Architecture: Safety redundancy, integrated safety shutdown
Resolution: 12 bits (4095 steps)
Load capacity:
Source mode: ≤ 550Ω (including line resistance)
Sensing mode: ≤ ((UQ - 10V) / 2) / 21.2mA (UQ = 10~30V DC)
Accuracy:
Basic error: ≤ ±0.2% FS (40μA) @ 25℃
Operating error: ≤ ±0.4% FS @ 0~+60℃
Isolation withstand voltage: 250V AC (channel to analog ground)
Power supply: 5V DC ≈ 85mA; 24V DC≈130mA
Operating temperature: -20℃ ~ +60℃
Dimensions/Weight: 4TE (25×203×127mm) / Approximately 0.5kg
Installation: DIN rail, supports hot swapping
Diagnosis: Output short circuit / open circuit / over-range detection, automatic full test during operation
II. Relationship with the standard version F6705 (984670501)
F670532 (984670532): Hardware/firmware upgrade, enhanced diagnostics and stability, batch update, fully interchangeable
F6705 (984670501): Standard version, functionally identical
III. Key points (Installation / Wiring / Maintenance)
1. Installation essentials
Environment: Dust-free, dry, free from corrosion, anti-condensation
Heat dissipation: Maintain a spacing of ≥ 50mm between top and bottom, keep away from heat sources and strong electricity
Grounding: Independent protection ground of the cabinet ≤ 4Ω, separate system ground from protection ground
Hot swapping: Before online replacement, disable the module in the software
2. Wiring specifications (28-pin terminals)
Signal cables: Shielded twisted pair, single-ended grounding (module side)
Cabling: Separate the wiring from strong electricity by ≥ 10cm, avoid long parallel runs
Maximum cable length: 1000m (load resistance needs to be verified)
3. Configuration and calibration
Software configuration: ELOP II sets output type, range and fault safety value
Calibration cycle: Suggested once a year; re-calibrate if error exceeds ±0.2% FS
Safety shutdown: Automatically cuts off output and enters safe state upon failure
4. Maintenance and fault troubleshooting
Status indication: Green LED = normal, red = fault; regularly check diagnostic logs
Common faults:
Incorrect output: Check wiring, shielding, grounding and load resistance
No output from channel: Check short circuit / open circuit, replace the channel for testing, if abnormal, replace the module

Get a Quote